33
■
Induced draft
blower runs
continuously
with no further
furnace
operation.
■
Integrated
control module
LED display
provides “E2”
error code.
E2
■
Low-stage
pressure switch
circuit is not
closed.
■
Pressure switch
hose blocked,
pinched or
connected
improperly.
■
Blocked flue and/or
inlet air pipe,
blocked drain
system or weak
induced draft
blower.
■
Incorrect pressure
switch setpoint or
malfunctioning
switch contacts.
■
Loose or
improperly
connected wiring.
■
Inspect pressure
switch hose. Repair/
replace, if necessary,
■
Inspect flue and/or
inlet air piping for
blockage, proper
length, elbows and
termination.
■
Check drain system.
Correct as necessary.
■
Check induced draft
blower performance.
Correct as necessary.
■
Correct pressure
switch setpoint or
contact motion.
■
Tighten or correct
wiring connection.
■
Turn off power prior to
repair.
■
Replace pressure
switch with correct
replacement part.
■
Replace induced draft
blower with correct
replacement part.
■
Circulator
blower runs
continuously.
No furnace
operation.
■
Integrated
control module
LED display
provides “E3”
error code.
E3
■
Primary limit or
auxiliary limit
circuit is open.
■
Rollout limit
circuit is open.
■
Insufficient
conditioned air
over the heat
exchanger.
Blocked filters,
restrictive
ductwork, improper
circulator blower
speed, or failed
circulator blower.
■
Flame rollout.
■
Misaligned
burners, blocked
flue and/or air inlet
pipe or failed
induced draft
blower.
■
Loose or
improperly
connected wiring.
■
Check filters and
ductwork for blockage.
Clean filters or remove
obstruction.
■
Check circulator
blower speed and
performance. Correct
speed or replace
blower if necessary.
■
Check burners for
proper alignment.
■
Check flue and air inlet
piping for blockage,
proper length, elbows
and termination.
Correct as necessary.
■
Check induced draft
blower for proper
performance. Replace,
if necessary.
■
Tighten or correct
wiring connection.
■
Turn off power prior to
repair.
■
See Specification
Sheet applicable to
your model for
allowable rise range
and proper circulator
speed.
■
See “Vent/Flue Pipe”
section for piping
details.
■
Induced draft
blower and
circulator
blower runs
continuously.
No furnace
operation.
■
Integrated
control module
LED display
provides “E4”
error code.
E4
■
Flame sensed
with no call for
heat.
■
Short to ground in
flame sense circuit.
■
Lingering burner
flame.
■
Slow closing gas
control valve.
■
Correct short at flame
sensor or in flame
sensor wiring.
■
Check for lingering
flame.
■
Verify proper operation
of gas control valve
■
Turn off power prior to
repair.
■
No furnace
operation.
■
Integrated
control module
LED display
provides “E5”
error code.
E5
■
Open fuse.
■
Short in low voltage
wiring.
■
Locate and correct
short in low voltage
wiring.
■
Turn off power prior to
repair.
■
Replace fuse with 3A
automotive fuse.
Symptoms of
Abnormal
Operation
Diagnostic/
Staus LED
Code
Fault Description Possible Causes
Corrective Actions
Notes and Cautions