4-wire receptacle 

(14-30R)

ELECTRIC DRYER POWER HOOKUP- 

CANADA ONLY

ELECTRICAL REQUIREMENTS

It is your responsibility: 

 

To contact a qualified electrical installer.

 

To be sure that the electrical connection is adequate and in 

conformance with Canadian Electrical Code, C22.1-latest 

edition and all local codes. A copy of above codes standard 

may be obtained from: Canadian Standards Association,  

178 Rexdale Blvd., Toronto, ON M9W 1R3 CANADA.

 

To supply the required 4-wire, single phase, 120/240 volt,  

60 Hz, AC only electrical supply on a separate 30-amp 

circuit, fused on both sides of the line.  A time-delay fuse or 

circuit breaker is recommended. Connect to an individual 

branch circuit. 

 

This dryer is equipped with a CSA  

International Certified Power Cord  

intended to be plugged into a standard  

14-30R wall receptacle. The cord is  

5 ft. (1.52 m) long. Be sure wall receptacle  

is within reach of dryer’s final location.

For further information, please reference service numbers located 

in “Assistance or Service” section of your “Use and Care Guide.”

GROUNDING INSTRUCTIONS

SAVE THESE INSTRUCTIONS

■  

For a grounded, cord-connected dryer: 

This dryer must be grounded. In the event of malfunction or 
breakdown, grounding will reduce the risk of electric shock 
by providing a path of least resistance for electric current. 
This dryer is equipped with a cord having an equipment- 
grounding conductor and a grounding plug. The plug must 
be plugged into an appropriate outlet that is properly 
installed and grounded in accordance with all local codes 
and ordinances.

WARNING:

 

Improper connection of the equipment- 

grounding conductor can result in a risk of electric shock. 
Check with a qualified electrician or service representative 
or personnel if you are in doubt as to whether the dryer is 
properly grounded. Do not modify the plug provided with 
the dryer: if it will not fit the outlet, have a proper outlet 
installed by a qualified electrician.

4-wire 

receptacle 

(14-30R)

If your outlet looks like this:

Then choose a 4-wire power supply cord with 

ring or spade terminals and UL listed strain 

relief. The 4-wire power supply cord, at least  

4 ft. (1.22 m) long, must have 4 10-gauge solid 

copper wires and match a 4-wire receptacle of 

NEMA Type 14-30 R. The ground wire (ground 

conductor) may be either green or bare. The 

neutral conductor must be identified by a  

white cover.

3-wire 

receptacle 

(10-30R)

If your outlet looks like this:

Then choose a 3-wire power supply cord with 

ring or spade terminals and UL listed strain 

relief. The 3-wire power supply cord, at least  

4 ft. (1.22 m) long, must have 3 10-gauge solid 

copper wires and match a 3-wire receptacle of 

NEMA Type 10-30R.

If connecting by direct wire:

Power supply cable must match power supply (4-wire or 3-wire) 

and be:

 

Flexible armored cable or nonmetallic sheathed copper 

cable (with ground wire), covered with flexible metallic 

conduit. All current-carrying wires must be insulated.

 

10-gauge solid copper wire (do not use aluminum) at  

least 5 ft. (1.52 m) long.

Summary of Contents for WGD9500EW

Page 1: ...________________________________ Numéro de série ___________________________________ NOTES CONCERNANT L INSTALLATION Table des matières SÉCURITÉ DE LA SÉCHEUSE 25 EXIGENCES D INSTALLATION 27 Outillage et pièces 27 EXIGENCES D EMPLACEMENT 28 Distances de dégagement à respecter pour l installation 28 Dimensions de la sécheuse 28 RACCORDEMENT DE LA SÉCHEUSE ÉLECTRIQUE CANADA SEULEMENT 29 Spécificatio...

Page 2: ...2 DRYER SAFETY IMPORTANT When discarding or storing your old clothes dryer remove the door ...

Page 3: ...3 ...

Page 4: ...254 mm adjustable wrench for gas connections Pipe joint compound resistant to LP gas Plastic putty knife INSTALLATION REQUIREMENTS Leveling legs 4 Tape measure Pliers Parts supplied steam models Y connector Short inlet hose 5 1 52 m inlet hose Rubber washer 4 Parts needed steam models Parts package is located in dryer drum Check that all parts are included If using a power supply cord Use a UL lis...

Page 5: ... IMPORTANT Do not operate install or store dryer where it will be exposed to water weather or at temperatures below 45 F 7 C Lower temperatures may cause dryer not to shut off at end of automatic sensor cycles resulting in longer drying times NOTE No other fuel burning appliance can be installed in the same closet as a dryer DRYER DIMENSIONS INSTALLATION CLEARANCES For each arrangement consider al...

Page 6: ...e that the ground path is adequate If using a power supply cord Use a UL listed power supply cord kit marked for use with clothes dryers The kit should contain A UL listed 30 amp power supply cord rated 120 240 volt minimum with a temperature rating of 140 F 60 C minimum The cord should be type SRD or SRDT and be at least 4 ft 1 22 m long The wires that connect to the dryer must end in ring termin...

Page 7: ...ding plug The plug must be plugged into an appropriate outlet that is properly installed and grounded in accordance with all local codes and ordinances WARNING Improper connection of the equipment grounding conductor can result in a risk of electric shock Check with a qualified electrician or service representative or personnel if you are in doubt as to whether the dryer is properly grounded Do no...

Page 8: ...ed tapping accessible for test gauge connection immediately upstream of the gas connection to the dryer 1 2 IPS pipe is recommended 3 8 approved aluminum or copper tubing is acceptable for lengths under 20 ft 6 1 m if local codes and gas supplier permit If you are using Natural gas do not use copper tubing GAS SUPPLY REQUIREMENTS GAS DRYER POWER HOOKUP U S A AND CANADA ELECTRICAL REQUIREMENTS 120 ...

Page 9: ...is more than 20 ft 6 1 m use larger pipe NOTE Pipe joint compounds that resist the action of LP gas must be used Do not use TEFLON tape Must include shut off valve In the U S A An individual manual shut off valve must be installed within six 6 ft 1 8 m of the dryer in accordance with the National Fuel Gas Code ANSI Z223 1 The location should be easy to reach for opening and closing In Canada An in...

Page 10: ...ct wire connection 2 Remove terminal block cover Remove hold down screw and terminal block cover Put power supply cord through the strain relief Be sure that the wire insulation on the power supply cord is inside the strain relief The strain relief should have a tight fit with the dryer cabinet and be in a horizontal position Do not further tighten strain relief screws at this point Attach power s...

Page 11: ... B Remove neutral ground wire E from external ground conductor screw A Reinstall ground conductor screw A B A E Prepare to connect neutral ground wire and neutral wire 1 B E C Connect neutral ground wire and neutral wire 2 Connect neutral ground wire E and neutral wire white C of power supply cord under center terminal block screw B Tighten screw Connect remaining wires 4 Connect remaining wires t...

Page 12: ...einsert tab of terminal block cover into slot of dryer rear panel Secure cover with hold down screw Now go to Venting Requirements 2 Connect neutral wire Connect neutral wire white or center C of power supply cord to center terminal block screw B Tighten screw B C Remove center terminal block screw B B 1 Remove center screw Unscrew the removable conduit connector A and any screws from a 3 4 19 mm ...

Page 13: ... from remaining 3 wires Strip insulation back 1 25 mm Shape ends of wires into hooks 3 89 mm 5 127 mm 1 Prepare your 4 wire cable for direct connection B E C 3 Connect neutral ground wire and neutral wire Connect neutral ground wire E and place hooked end hook facing right of neutral wire white or center wire C of direct wire cable under center screw of terminal block B Squeeze hooked ends togethe...

Page 14: ... moved if needed Strip 31 2 89 mm of outer covering from end of cable Strip insulation back 1 25 mm If using 3 wire cable with ground wire cut bare wire even with outer covering Shape wire ends into hooks 1 25 mm 3 89 mm 1 Prepare your 3 wire cable for direct connection Connect remaining wires 4 Place hooked ends of remaining direct wire cable wires under outer terminal block screws hooks facing r...

Page 15: ... neutral wire 2 Connect neutral ground wire E and neutral wire white or center wire C of power supply cord or cable under center terminal block screw B Tighten screw Connect remaining wires 3 Connect remaining wires to outer terminal block screws Tighten screws A G Connect external ground wire 4 Connect a separate copper ground wire G from the external ground conductor screw A to an adequate groun...

Page 16: ...stem and make sure exhaust hood is not plugged with lint Replace plastic or metal foil vents with rigid metal or flexible metal vents Review Vent System Chart and if necessary modify existing vent system to achieve best drying performance VENTING Connect gas supply to dryer 1 Remove red cap from gas pipe Using a wrench to tighten connect gas supply to dryer Use pipe joint compound on threads of al...

Page 17: ... 12 305 mm from ground or any object that may obstruct exhaust such as flowers rocks bushes or snow Acceptable Style Optional exhaust installations PLAN VENT SYSTEM Recommended exhaust installations Typical installations vent the dryer from the rear of the dryer Other installations are possible A Dryer B Elbow C Wall D Exhaust hood E Clamps F Rigid metal or flexible metal vent G Vent length necess...

Page 18: ... to determine type of vent material and hood combinations acceptable to use NOTE Do not use vent runs longer than those specified in Vent System Chart Exhaust systems longer than those specified will Shorten life of dryer Reduce performance resulting in longer drying times and increased energy usage Vent System Chart Number of 90 elbows Type of vent Angled hoods 1 4 3 2 0 Rigid metal Rigid metal R...

Page 19: ...er cold inlet hose to other side of Y connector Screw on coupling by hand until it is seated on connector Using pliers tighten the couplings an additional two thirds turn NOTE Do not overtighten Damage to the coupling can result 57 8 150 mm 41 2 115 mm Attach long hose to dryer fill valve and tighten coupling 5 Attach other end of long hose to fill valve at bottom of dryer back panel Screw on coup...

Page 20: ...xhaust outlet and inside exhaust hood Check that vent is secured to exhaust hood with a 4 102 mm clamp Move dryer to final location 2 Move dryer to final location Avoid crushing or kinking vent Level Dryer 1 Adjust leveling legs 2 If dryer is not level prop up using a wood block Use wrench to adjust legs up or down and check again for levelness For mobile home use Gas dryers must be securely faste...

Page 21: ...of scale through the water system in the dryer Over time the buildup of lime scale may clog different parts of the water system which will reduce product performance Excessive scale buildup may lead to the need for certain part replacement or repair All Models q Select a Timed Dry heated cycle and start dryer Do not select Air Only Temperature setting If dryer will not start check the following Co...

Page 22: ...o avoid damaging the dryer s surface or the dryer door Remove door from dryer cabinet 1 Open the dryer door 2 Use a plastic putty knife to remove the hinge covers and plastic covers from the front panel of the dryer Set them aside 4 Remove the dryer door from the cabinet by lifting upward and out Lay the door on a towel or a soft cloth you placed on a flat workspace Tools needed Min 8 long TORX T2...

Page 23: ...A A B A A B 7 Using a 2 Phillips screwdriver remove the screws from the opposite side and set them aside Then using a plastic putty knife remove the door latch from the top of the door by gently pushing in the metal tab and lifting Repeat for the top and remove the latch REINSTALL HINGES ON DOOR After removing the door latch move it to the opposite side place it in the open slot and press it until...

Page 24: ...IKE 1 Using a T20 screwdriver remove the two screws securing the door strike and move the door strike from the left side of the dryer cabinet to the right side securing it with the removed screws 2 Hang the door on the unit by placing set pin in dryer cabinet hole and sliding door down Using a Phillips screwdriver install screws 1 and 3 and then screws 2 and 4 Tighten all hinge screws ...

Page 25: ...43 NOTES ...

Page 26: ...W10757741A W10757742A SP 09 15 2015 All rights reserved Tous droits réservés ...

Reviews: