22
ELECTRIC DRYER ELECTRICAL CONNECTIONS
(FOR U.S.A. ONLY)
Connecting 3-Wire Connection: Optional
2.
Place hooked end of neutral wire (white or center wire)
(D) of direct wire cable under center terminal block screw
(A), hook facing right. Squeeze hooked end together and
tighten screw.
3.
Connect remaining wires under outer terminal block
screws (F). Squeeze hooked ends together and tighten
screws. Finally, reinstall terminal block cover to dryer rear
panel. Secure cover with hold-down screw. Now go to
"Venting Requirements."
Use where local codes permit connecting cabinet-ground
conductor to neutral wire.
Direct wire cable must have 5 ft. (1.52 m) of extra length so
dryer can be moved if needed.
Strip 3½" (89 mm) of outer covering from end of cable. Strip
insulation back 1" (25 mm). If using 3-wire cable with ground
wire, cut bare wire even with outer covering. Shape ends of
wires into a hook shape.
Connecting Neutral Wire
1.
Loosen or remove center terminal block screw (A).
Connecting 3-Wire Connection: Direct Wire
A
A
D
F
F
3.
Connect remaining wires under outer terminal block screws
(F). Tighten screws.
4.
Connect a separate copper ground wire (G) under the
green external ground conductor screw (C) to an adequate
ground. Finally, reinstall terminal block to dryer rear panel.
Secure cover with hold-down screw. Now go to "Venting
Requirements."
Use for direct wire or power supply cord where local codes
do not permit connecting cabinet-ground conductor to
neutral wire.
1.
Remove center terminal block screw (A). Also remove
neutral ground wire (B) by removing green external ground
conductor screw (C).
2.
Connect neutral ground wire (B) and neutral wire (white or
center wire) (D) of power supply cord/cable under center
terminal block screw (A). Tighten screw.
A
B
A
B
D
C
G
C
F
F
E