PROBABLE CAUSE
CORRECTION
PROBLEM
11. Moisture dripping
into room
12. Excess conden-
sation running out-
side
11a.
Extreme humidity
11b.
Inadequate seal
11c.
Improper level
12. Extreme humidity
11a.
Advise customer of pos-
sible sweating formations under
abnormal conditions. Check and
improve all possible seals.
11b.
Check and improve all
sealed areas.
11c.
Check for proper side to
side level of unit. Check for (½”
rear slope (or 1 full bubble) on
level.
12. This condition is normal in
areas of extreme humidity.
TROUBLESHOOTING CHART
COMPRESSOR SPECIFICATIONS
Part Number
8040122
8040126
Capacity (Btu/hr)
5,160
6,745
Watts
465
615
Run Resistance
1.469
1.130
Start Resistance
2.373
2.712
Table 1
Table 2
PROPER LOCATION OF THERMISTOR
The thermistor must be properly mounted on
the front surface of the evaporator.
VERTICAL LOCATION: The plastic thermistor
mounting bracket should be located on the
fourth tube from the top as shown in the illus-
tration.
HORIZONTAL LOCATION: The right end of
the plastic thermistor mounting bracket should
be located 6½” from the evaporator frame as
shown in the illustration. The end of the ther-
mistor should be located 7½” from the evapo-
rator frame.
7½”
6½”
FAN MOTOR SPECIFICATIONS
Part Number
8040173
Capacity (Btu/hr)
5,160 to 6,745
Turbo Speed
32.4
Ω
Hi Speed
40.4
Ω
Low Speed
20.4
Ω