background image

TECH SHEET - DO NOT DISCARD

PAGE 3

FOR SERVICE TECHNICIAN'S USE ONLY

PART NO. 3979119

–  BELT/BELT SWITCH
–  MOTOR
–  DOOR SWITCH
–  EVEN HEAT CONTROL

IMPORTANT:

Electrostatic (static elec-

tricity) discharge may cause damage to

electronic control assemblies. See page 1

for details.

Procedure:

1.

Set the following configuration:

Door - must be closed

Timer - TIMED DRY

Fabric Care/Temperature switch -

AIR FLUFF

2.

Check connector pins in P2 at the Even

Heat Control to make sure they are making

contact.

3.

Check the voltage at the Timer (reference

Neutral):

a.

At Timer BK voltage should be 120VAC.

If not, check the input voltage line (L1).

b.

If voltage is present at BK, check Timer

voltage at BU. If voltage is not 120VAC,

replace the Timer.

4.

Check for 120VAC at the PTS switch and

Motor Relay. 120VAC (reference Neutral)

should be present at:

one side of the PTS switch

one side of the Motor Relay contacts

(large terminals)

If 120VAC is not present at these locations,

check the harness connections. If harness

connections are good, go to Step 5.

5.

Press and hold the PTS switch.

a.

Check the voltage at the PTS switch. If

120VAC is not present at both terminals,

replace PTS switch.

b.

Check the voltage at the Motor Relay:

Both sides of the Motor Relay contacts

(large terminals) should be 120VAC with

reference to Neutral.
If 120VAC is not present at one of the

Motor Relay contacts, then check for

48VDC from P2-7 to P3-2. If 48VDC is

correctly shown, replace the Motor Re-

lay. If not 48VDC, then replace the Even

Heat Control Assembly.

6.

If the motor does not start, check the Door

switch (D to D1). There should be continu-

ity when the door is closed. If not, replace

the Door switch.

7.

Press the PTS switch. If the motor starts but

does not continue to run, replace the Even

Heat Control Assembly.

8.

Press and hold the PTS switch. If motor

does not start, replace the motor.

PROBLEM: Dryer Will Not Heat

(Refer to Heater Strip Circuit, page 6)

If the heat will not turn on, check the following:

LINE VOLTAGE (120V)

HARNESS/CONNECTION

HEATER RELAY

THERMAL FUSE

HIGH LIMIT THERMOSTAT

HEATER

–  CENTRIFUGAL SWITCH
–  THERMISTOR

EVEN HEAT CONTROL

IMPORTANT:

Electrostatic (static elec-

tricity) discharge may cause damage to

electronic control assemblies. See page 1

for details.

Procedure:

1.

Set the following configuration:

Door - must be closed

Fabric Care/Temperature switch -

COTTON / TOWELS

Timer - TIMED DRY

2.

Press the PTS switch. The dryer will start,

and the heater will take several seconds to

turn on.

3.

Check the voltage at the Heater Relay:

P3-1 to P3-2 should be 48VDC

COM to NO should be ~0VAC

a.

If the voltage is 48VDC at the P3-1 to

P3-2 terminals, and ~120VAC at the

COM and NO terminals, replace the

Relay.

b.

If the voltage is 0VDC at the P3-1 to P3-2

terminals, replace the thermistor.

c.

If, after replacing the thermistor, the

voltage is still 0VDC at the P3-1 to P3-2

terminals, replace the Even Heat Control

Assembly.

PROBLEM: Dryer Heats During

Air Fluff/No Heat Cycle

(Refer to Heater Strip Circuit, page 6)

If the dryer heats when the Fabric Care/Tem-

perature switch is set to AIR FLUFF (No Heat),

check the following:

–  HARNESS/CONNECTION
–  HEATER RELAY
–  FABRIC CARE SWITCH
–  EVEN HEAT CONTROL

IMPORTANT:

Electrostatic (static elec-

tricity) discharge may cause damage to

electronic control assemblies. See page 1

for details.

Procedure:

1.

Perform the Fabric Care/Temperature Switch

Test on page 2.

2.

Set the following configuration:

Door - must be closed

Fabric Care/Temperature switch -

AIR FLUFF

Timer - TIMED DRY

3.

Press the PTS switch.

a.

Check voltage on Heater Relay. If P3-1

to P3-2 is 0VDC, replace the Heater

Relay.

b.

If P3-1 to P3-2 is 48VDC, replace the

Even Heat Control Assembly.

PROBLEM: Dryer Won’t Shut

Off

(Refer to Motor and Moisture

Sensor Strip Circuits, page 6)

If the dryer will not shut off, check the following:

PUSH TO START (PTS) SWITCH

HARNESS/CONNECTION

MOTOR RELAY

–  MOISTURE SENSOR
–  EVEN HEAT CONTROL

IMPORTANT:

Electrostatic (static elec-

tricity) discharge may cause damage to

electronic control assemblies. See page 1

for details.

Procedure:

1.

Set the Timer to OFF. If the dryer starts run-

ning as soon as it is plugged in, replace the

Timer.

2.

Set the following configuration:

Dryer - power cord plugged in

Door - must be closed

Fabric Care/Temperature switch -

COTTON / TOWELS

Timer - TIMED DRY for less than 10

minutes

3.

If the dryer starts running before the PTS

switch is pressed, replace the PTS switch.

4.

If, after replacing the PTS switch, the dryer

still starts before the PTS switch is pressed,

replace the Motor Relay.

5.

If the dryer does not stop after the set time

elapses, check the Motor Relay.

a.

If the voltage is 0VAC at COM to NO,

replace the Motor Relay.

b.

If the voltage is 120VAC at COM to NO,

replace the Even Heat Control Assembly.

6.

If the dryer will not terminate its cycle when

set to AUTO MOISTURE SENSING PLUS,

check the Moisture Sensor.

a.

If there is continuity to Ground for Yellow/

Red (Y/R) wire with no load, look for a

short in the Sensor or Y/R wire. Verify

harness connections both at the Sensor

and the Even Heat control.

b.

If the Sensor and Y/R wire are good, re-

place the Even Heat Control Assembly.

PROBLEM: Dryer Shuts Off

Before Clothes Are Dry

(Refer to Thermistor Test, page 2, and
Moisture Sensor Strip Circuit, page 6)

If the dryer shuts off too soon when set to the

AUTO MOISTURE SENSING PLUS cycle,

check the following:

–  HARNESS/CONNECTION
–  MOISTURE SENSOR
–  THERMISTOR
–  EVEN HEAT CONTROL

IMPORTANT:

Electrostatic (static elec-

tricity) discharge may cause damage to

electronic control assemblies. See page 1

for details.

Procedure:

1.

Test the Moisture Sensor by following the

procedure outlined in “Factory Test”,

beginning on page 1. If the Moisture Sen-

sor fails the “Factory Test” (does not pro-

duce a beep sound), check the Moisture

Sensor.

Summary of Contents for 72972

Page 1: ...ouble beep pause triple beep will sound to indicate that the factory test mode is activated NOTE If any of these initial conditions are not satisfied the control will not enter the test mode Test Mode Functionality When the control is in the Factory Test mode every input change of state will result in a beep with the exception of the Signal switch This includes Door switch Moisture Sensor short op...

Page 2: ...ed temperature Procedure Begin with an empty dryer and a clean lint screen 1 Set the following configuration Timer Dial TIMED DRY Fabric Care Temperature switch COTTON TOWELS HIGH Wrinkle Guard switch OFF Signal switch HIGH Door must be closed 2 Press the Push To Start PTS switch a If you hear three short beeps and the dryer shuts off after several seconds the thermistor or wire harness is either ...

Page 3: ...lacing the thermistor the voltage is still 0VDC at the P3 1 to P3 2 terminals replace the Even Heat Control Assembly PROBLEM Dryer Heats During Air Fluff No Heat Cycle Refer to Heater Strip Circuit page 6 If the dryer heats when the Fabric Care Tem perature switch is set to AIR FLUFF No Heat check the following HARNESS CONNECTION HEATER RELAY FABRIC CARE SWITCH EVEN HEAT CONTROL IMPORTANT Electros...

Page 4: ...5152 3405152 Fabric Care Temperature Switch 3399643 3399643 3399643 Motor Relay 3405281 3405281 3405281 Heater Relay 3405281 3405281 3405281 Even Heat Control Assembly 3976627 3976627 3976627 Timer Knob and Skirt 3402598 3402597 3402595 Console Harness 3976590 3976590 3976590 Main Harness 8299935 8299935 8299935 Door Switch 3392266 3392266 3392266 Thermal Fuse 3390719 3390719 3390719 Gas Burner As...

Page 5: ...ER HI P3 1 HEATER LOW RED COM NO R W R W LOUD BLUE P2 7 BLUE PK BK PTS MOTOR RELAY PK BK BU BLK BU BLK COM NO MOTOR START START SENSE BU BK P1 5 RED WHITE RED CENTRIFUGAL SWITCH P4 5 P4 4 WET W R P4 8 DAMP BLK P4 6 COOL DOWN W BL P4 7 W V P4 3 P4 2 P4 1 BLK BLK L1_ RETURN W R WH BLUE Gas Dryer Wiring Diagram IMPORTANT Electrostatic static electricity discharge may cause damage to electronic contro...

Page 6: ... SWITCH RED WHITE 5M 6M THERMISTOR RED THERMAL FUSE 196 F HIGH LIMIT THERMOSTAT 205 F TEMP NEUTRAL P2 3 P2 1 NC 3M D D2 D1 RED WHITE WHITE WHITE RED W R 3V BLUE 1V HS1 HS2 TF1 TF2 EVEN HEAT CONTROL HEATER RELAY P3 2 HEATER HI P3 1 HEATER LOW RED COM NO R W R W BLUE CENTRIFUGAL SWITCH HEATER STRIP CIRCUIT BLACK L1 LINE WHITE N NEUTRAL EVEN HEAT CONTROL NEUTRAL TERMINAL LINKED TO CABINET MOIST GND M...

Reviews: