TROUBLESHOOTING: 

 
 

The SP4-RMX contain yellow LED indicators that, when illuminated, indicate a trouble condition. A trouble condition will also occur 
on the SP40/2. 
 
 

LED trouble indication on the SP40/2 when the SP4-RMX is connected to it  

 
 

The D13 TRB LED indicator and D49 AUX IN LED indicator on the SP40/2 will illuminate when the SP4-RMX has a trouble 
condition.  
 
 

LED trouble indications on the SP40/2 and SP4-RMX when the SPB indicates a trouble condition  

 
The D13 TRB LED indicator and D54 AUDIO SHORT LED indicator on the SP40/2 will illuminate; D29 SYS TRB and D23 WIRE 
SHT on the SP4-RMX when the SPB has a trouble condition. 

 
 

Use the following troubleshooting table to locate the trouble area. 

 
 

Table 4: 

Trouble LED Indicators 

 

D30 SYS 
PWR 

D29 SYS 
TRB 

LED 
Indicator 

Remarks 

ON OFF  

Normal 

OFF 

OFF 

 

24VDC not applied. Check PWR IN terminals. If 24VDC is present then SP4-RMS 
module is defective. Replace. 

 

RM CC input shorted in excess of 2 1/2 minutes or Defective SP4-RMX module. 

D22 WIRE 
Open 

AUD OUT circuit open or 10K Ohm EOLR missing. 

D23 WIRE 
SHT 

AUD OUT circuit shorted. 

D24 AUX 
TRB 

AUX IN circuit open or 10K Ohm EOLR missing. 

D25 ALM 
TRB 

ALM TRB circuit open or 10K Ohm EOLR missing. 

D26 RM1 
TRB 

RM1 CC circuit open or RM1 module in trouble condition. 

D27 RM2 
TRB 

RM2 CC circuit open or RM2 module in trouble condition. 

ON ON 

D28 RM3 
TRB 

RM3 CC circuit open or RM3 module in trouble condition. 

 
Malfunctioning modules should be returned to the manufacturer for repair or replacement. 

Summary of Contents for SP4-RMX

Page 1: ...e number of optional Remote Microphones SPRM or SPRM GP to three The PCB assembly is mounted in an enclosure READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT NOTE All CAUTIONS and WARNINGS...

Page 2: ...out basis Technical Specifications Electrical Input Voltage 24 VDC Input Current 52mA max RM Page 62mA max Standby Auxiliary Audio Input 1Vrms Relay Ratings K1 and K3 2A 30Vdc 1pF K2 K4 K5 and K6 1A...

Page 3: ...o all qualified personnel who operate test maintain or service SAFEPATH4 products 2 Carefully unpack the SP4 RMX and make sure each item described on the packing slip is present and undamaged 3 Mount...

Page 4: ...MX Cable Size 14 22 AWG Shielded One end of the shield must be connected at the SafePath4 panel or SP4 RMX enclosure Maximum Length 20 Feet Restrictions All wiring between SP40 2 or Audio Booster and...

Page 5: ...P84557 D Sheet 5 of 14 6 00 CONDUITKNOCKOUTS 2 PLACES BOTHENDS 11 00 MOUNTINGHOLES MOUNTINGHOLES GROUND TERMINALS Figure 2 SP4 RMX Mounting NOTE Drawing is not to scale...

Page 6: ...J1 ALL CONNECTIONS BETWEEN SP40 AND RMX ARE SUPERVISED THESE CONNECTIONS MUST BE RUN IN NO MORE THAN 20 FT OF CONDUIT AND WITHIN THE SAME ROOM ALL CONNECTIONS BETWEEN RMX AND REMOTE MICS ARE SUPERVIS...

Page 7: ...RMX Modules 10K EOLR AUX IN CC NAC SP40 2 24 VDC 10K EOLR 10K EOLR 10K EOLR 10K EOLR S3 S2 S3 SW2 RM3 VOL RM2 VOL RM1 VOL 1V 25V 70V AUX VOL R37 J1 S3 S2 S1 SW2 RM3 VOL RM2 VOL RM1 VOL 1V 25V 70V AUX...

Page 8: ...HESE CONNECTIONS MUST BE RUN IN NO MORE THAN 20FT OF CONDUIT AND WITHIN THE SAME ROOM REFER TO FIGURE 3 FOR SPRM G P CONNEC TIONS ALL CONNEC TIONS ARE SUPERV ISED SP40 2 SP4 RMX SPB 10K OHM EOLR 10K O...

Page 9: ...SPRM connected Insure the corresponding switch is OFF for any SPRM inputs not used Set switch S1 on SW2 to the desired position according to Table 1 Set S2 to ON Switch S3 to the ON position Set switc...

Page 10: ...of the SP40 2 and SPB audio boosters In SP40 mode each SP4 RMX provides the capability of connecting and supervising up to three SPRM emergency remote microphone modules In SPB mode the SPRM GP Gener...

Page 11: ...o booster modules the SP40 2 AUDIO OUT is connected to the SP4 RMX AUX IN and the SP4 RMX AUDIO OUT is connected to the SPB AUDIO IN This means that the priority level of the SPRM GP modules are after...

Page 12: ...Use the following troubleshooting table to locate the trouble area Table 4 Trouble LED Indicators D30 SYS PWR D29 SYS TRB LED Indicator Remarks ON OFF Normal OFF OFF 24VDC not applied Check PWR IN ter...

Page 13: ...13 of 14 S3 S2 S1 SW2 RM3 VOL RM2 VOL RM1 VOL 1V 25V 70V AUX VOL R37 J1 AUX TRB ALM TRB RM1 TRB WIRE SHT WIRE OPEN SYS TRB SYS PWR D24 D25 D26 D27 D28 D23 D22 D29 D30 RM2 TRB RM3 TRB Figure 6 SP4 RMX...

Page 14: ...SPECIFICATION ABUSE ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK S CONTROL SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE WITH RESPECT TO THOSE PRODUCTS WHEELOCK DOES NOT WARRANTY THAT THE OPERATI...

Reviews: