P84557
D
Sheet 11 of 14
Priority Levels on SP40/2 with SP4-RMX Connected
Table 2:
Priority Levels SP40/2 to SP4-RMX
Priority Source
Remarks
1
SP40/2 Onboard Mic
2
SPRM #1 or First In First Out
3
SPRM #2 or First In First Out
4
SPRM #3 or First In First Out
Can be configured to operate as First
In First Out
5
AUX IN or Second SP4-RMX
Can be configured to operate as First
In First Out
6 to 8
SP40/2 DV Messages from 3MEM module
9 to 11
SP40/2 DV Messages
IN1, IN2, IN3
12 to 14
SP40/2 Non Alarm Audio Outputs
NR, TEL, BGM
When the SP4-RMX is used for connecting SPRM modules to any of the SPB audio booster modules, the SP40/2 AUDIO OUT is
connected to the SP4-RMX AUX IN and the SP4-RMX AUDIO OUT is connected to the SPB AUDIO IN. This means that the
priority level of the SPRM-GP modules are after the digital voice messages on the SP40/2 and are considered non-alarm conditions.
Priority Levels on SPB with SP4-RMX Connected
Table 3
Priority Levels SP4-RMX to SPB
Priority Source
Remarks
1
SP40/2 Onboard Mic
2
SP40/2 AUX IN
Can be a single SPRM or an
SP4-RMX used for ALL CALL
3 to 5
SP40/2 DV Messages from 3MEM
module
6 to 8
SP40/2 DV Messages
IN1, IN2, IN3
9
SPRM-GP #1 or First In First Out
10
SPRM-GP #2 or First In First Out
11
SPRM-GP #3 or First In First Out
Can be configured to operate as
First In First Out. NOT FOR
EMERGENCY USE.
12 to 14
SP40/2 Non Alarm Audio Outputs
NR, TEL, BGM