Remote
SAFEPATH
Manual Sheet
49
of
50
Rev. C December 1998
Technical Specifications
Mechanical
Dimensions (H x W x D)
36" by 24" x 6"
Weight
90
pounds
Enclosure
0.050"
Steel
Finish
Black
Mounting Indoor
Surface
Mount
Top
and
Bottom
Wiring
Entry
Environmental
(Meets UL requirements)
Operating Temperature
0° to +49° C (32 to 120 Degrees F)
Storage Temperature
-20° to 70° C (-4 to 158 Degrees F)
Humidity
85±5% @ 30±2° C (86
±
4 Degrees F) Non-condensing
Electrical
Input
Voltage:
120VAC
Input Current (max): 8.0 at 120VAC
Outputs
Visual Notification
1 to 4 output channels optionally provided; each output is rated for
Appliance Output
2.0 Amps at 24V. Total of all output channels may not exceed 6.0 Amps.
Central Amplified
1 to 4 output channels optionally provided; each programmable for Audio
Output
either 25V, 70.7V or 100V output.
Amplified Speaker
1 to 4 output channels optionally provided; each through 15 Ohm
Audio
Output isolation
transformer. Output level is -5 dBm maximum
Amplified Speaker
1 to 4 output channels optionally provided; each output is rated for
Power Output
2.0 Amps at 24V.
Trouble
Audible
Output
is
rated for 0.100 Amps at 24VDC
Output
Status Contact
Form C contact normally energized. Contacts transfer during trouble.
Rated 0.5 Amps at 24VDC max, resistive load.
WARNING:
DO NOT EXCEED THE RATINGS OF THE STATUS CONTACT. EXCEEDING THE RATINGS MAY CAUSE
THE RELAY TO FAIL AND PREVENT A TROUBLE CONDITION FROM BEING INDICATED.
Alarm Contact
Form C contact normally de-energized. Contact transfers during alarm.
Rated 0.5 Amps at 24VDC max, resistive load.
WARNING:
DO NOT EXCEED THE RATINGS OF THE ALARM CONTACT. EXCEEDING THE RATINGS MAY CAUSE
THE RELAY TO FAIL AND PREVENT MESSAGES FROM BEING PLAYED.
Wiring Connections
Screw Terminals
Each terminal accepts one conductor from #22 to #12 AWG.
End-of-Line Resistor
Visual Notification
Appliance Outputs
10K, 1/8W Minimum, 5%
Audio Notification
Appliance Outputs
10K, 1W Minimum, 5%
Amplified Speaker
Appliance Power Outputs 10K, 1/8W Minimum, 5%
Limited Warranty
Wheelock products must be used within their published specifications and must be PROPERLY specified, applied,
installed, operated, maintained and operationally tested in accordance with these instructions at the time of
Summary of Contents for SAFEPATH RSAPE-B
Page 11: ...Remote SAFEPATH Manual Sheet 11 of 50 Rev C December 1998 Figure 2 Operator s Console ...
Page 16: ...Remote SAFEPATH Manual Sheet 16 of 50 Rev C December 1998 Figure 3 Panel Mounting ...
Page 41: ...Remote SAFEPATH Manual Sheet 41 of 50 Rev C December 1998 Figure 23 Panel Block Diagram ...