background image

 

273 Branchport Avenue

   

 

 

 

 

 

 

 

 

Thank you for using our products. 

Long Branch, NJ  07740 
(800) 

 

631-2148 

            INSTALLATION 

INSTRUCTIONS 

www.cooperwheelock.com 

       E50 

MULTI-CANDELA SPEAKER STROBES 

 

Use this product according to this instruction manual.  Please keep this instruction manual for future reference. 

 

GENERAL: 

The E50 Multi-Candela Speaker Strobes are UL Listed under Standard 1971 for Signaling Devices for the Hearing Impaired and UL Standard 1480 for Speaker 
Appliances.   The E50A Multi-Candela Speaker Strobe with amber lens is not UL approved.  They are designed for multiple power requirements with high dBA output 
at each power tap.  All models offer a choice of field selectable taps, 1/8W to 2W, for either 25.0VRMS or 70.0VRMS audio systems.  The design incorporates a high 
efficiency speaker for maximum output at minimum power across a frequency range of 400Hz to 4000Hz, and features a sealed back construction for extra protection 
and improved audibility.  The Speaker Strobes can provide non-synchronized strobe operation when connected directly to a Fire Alarm Control Panel (FACP), or 
provide synchronized strobe operation when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM), or Wheelock’s Power Supplies, PS-12/24-8MP 
and PS-12/24-8CP.  The E50-24MCW provides four selectable candela settings (15,30,75, & 110cd), and the E50-24MCWH provides two selectable settings (135 & 
185cd).  All models are UL Listed for 

indoor use only

 and 

wall mounting only

 with the backboxes specified in these instructions (see Mounting Options). 

NOTE:

  All 

CAUTIONS

 and 

WARNINGS

 are identified by the symbol 

.  All warnings are printed in bold capital letters. 

CAUTION:  

The speaker strobe appliance is a fire alarm device.  Do not paint 

WARNING:  PLEASE READ THESE INSTRUCTIONS CAREFULLY.  FAILURE TO COMPLY WITH ANY OF THE FOLLOWING 

INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF 
THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO 
YOU AND/OR OTHERS. 
 
SPECIFICATIONS: 

Table 1:  UL Listed Models and Ratings 

 Speaker 

Strobe  

Model Voltage 

(VRMS) 

dBA at 10 Feet 

 (Rated Watts) 

Regulated 

Voltage 

Voltage  

Range 

Candela 

(cd) 

Mounting 

Options 

 

 

1/8 1/4 1/2  1  2  (VDC/VRMS) 

(VDC/VRMS) 

 

 

E50-24MCW 

25/70 

77.0 79.5 82.5 85.0 88.0 

24 

16-33.0 

15/30/75/110 

A,B 

E50-24MCWH 

25/70 

77.0 79.5 82.5 85.0 88.0 

24 

16-33.0 

135/185 

A,B 

 
NOTES:   

1. 

Strobes will produce 1 flash per second over the “Regulated Voltage” range.    

2. 

All models are UL Listed for indoor use with a temperature range of +32ºF to +120ºF  (0ºC to +49ºC) and maximum humidity of 85% RH. 

3. 

dBA is rated per UL Standard 1480 for Speaker Appliances.  Frequency range of speakers is 400-4000Hz. 

4. 

For UL applications these appliances were tested to the operating voltage limits of 16-33 volts using Filtered (DC) or unfiltered Full-Wave-Rectified (FWR).  
Do not apply 80% and 110% of these voltage values for system operation. 

5. 

Check the minimum and maximum output of the power supply and standby battery and subtract the voltage drop from the circuit wiring resistance to 
determine the applied voltage to the strobes. 

6. 

Strobes with clear meet the required light distribution patterns defined in UL1971. 

7. 

Candela ratings are for clear lens.  Strobes with amber lens have 75% of the light output of clear lens. 

 

Table 2:  UL Current Rating for Strobe Only 

Maximum RMS Current (AMPS) 

UL 24MCW 

24MCWH 

Voltage 15cd 

30cd 

75cd 110cd 

135cd 

185cd 

DC 16-33VDC 

0.060  0.092  0.165  0.220  0.300  0.420 

FWR 16-33VRMS 

0.102 

0.155 

0.253 

0.347 

0.455 

0.645 

NOTE:  

Candela setting will determine the current draw of the product. 

 

NOTE:  

The maximum wire impendence between strobes shall not exceed 35 OHMS.  The maximum number of strobes on a single notification appliance circuit shall 

not exceed 47. 
 

CAUTION:  

Speaker

 

Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off. 

 

NOTE:  

Make sure that the total RMS current required by all appliances that are connected to the system’s primary and secondary power sources, NAC Circuits, SM, 

DSM, SYNC Modules or Wheelock Power Supplies do not exceed the power sources’ rated capacity or the current ratings of any fuses on the circuits to which these 
appliances are wired. 

 

WARNING:  OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO 

ALERT OCCUPANTS DURING AN EMERGENCY.  
 