NOTE
: Surface backbox (E50SSB) in Figure B, is compatible with wiremold and conduit. Mounting holes are for single-gang, double-gang, and #10 wood screws for
stud mounting. If metal conduit is installed onto top and bottom conduit entrances, then an insulated grounding wire (18 AWG, supplied) must be connected between
the top and bottom plate by using thread cutting screws (supplied) to provide electrical continuity per UL 50. See Figure 6.
Figure 6:
MOUNTING PROCEDURES:
CAUTION:
Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed
multiconductor cable or 3/4" conduit fittings are used.
1.
E50 models have an integrated Speaker Mounting Plate.
2.
The Speaker Mounting Plate must be oriented correctly when it is mounted to the backbox. Turn the Speaker Mounting Plate so that the arrow above the words
“Horizontal Strobe” points to the top side of the Speaker Mounting Plate.
3.
First mount the Speaker Mounting Plate to the backbox. Next slide the grille over the Speaker Mounting Plate strobe until both snaps are engaged.
4.
When terminating field wires, do not use more lead length than required. Excess lead length could result in insufficient wiring space for the signaling appliance.
5.
Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product.
6.
Do not pass additional wires (used for other than the signaling appliance) through the backbox. Such additional wires could result in insufficient wiring space for
the signaling appliance.
7.
Mounting hardware for each mounting option is supplied.
8.
All models can be flush mounted to a 4” square by 2-1/8” deep backbox in the wall (Figure A).
9.
Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product. This is
especially important for stiff, heavy gauge wires and wires with thick insulation or sheathing.
10
Use care to prevent speaker cone damage when driving screws for speaker product mounting.
WARNING: WHEN INSTALLING STROBES IN AN OPEN OFFICE OR OTHER AREAS CONTAINING PARTITIONS OR OTHER VIEWING
OBSTRUCTIONS, SPECIAL ATTENTION SHOULD BE GIVEN TO THE LOCATION OF THE STROBES SO THAT THEIR OPERATING EFFECT
CAN BE SEEN BY ALL INTENDED VIEWERS, WITH THE INTESITY, NUMBER, AND ILLUMINATION, REGARDLESS OF THE VIEWER’S
ORIENTATION.
The 110cd and 135/185cd settings are Listed for use in sleeping or non-sleeping areas when installed in accordance with appropriate NFPA Standards and the Authority
Having Jurisdiction.
WARNING: INSTALLERS MUST ADVISE OWNERS AND OPERATORS OF BUILDINGS WITH SLEEPING OCCUPANTS, E.G. HOTELS AND
MOTELS, TO WARN GUESTS, RESIDENTS AND EMPLOYEES TO NOT MOVE THE BED LOCATION TO A POSITION VIOLATING POINTS (1)
AND (2) ABOVE OR SERIOUS INJURY AND OR LOSS OF LIFE MAY OCCUR DURING A FIRE EMERENCY.