Fault
code
Fault
d
escription
Possible
r
eason
s
for
a
bnormality
How to
d
eal
w
ith
R
emarks
13 Compressor overheat
protector device
1.
The wiring of the overload
protector
is
connect
ed
loose
ly
.
2.
The overload protector fail
s
.
3.
The refrigerant is not enough;
4.
The installation pipe is
much
long
er
than
the
normal
one
, but
extra refrigerant
is not
add
ed
;
5.
The expansion valve
fails
;
6.
The outdoor control board
fails.
1. Reconnect the wiring of the
overload protector;
2. Replace the overload
protector;
3. Check the welding point of the
unit to confirm whether it is
leakage, and then recharge
the refrigerant;
4. Add the refrigerant;
5. Replace expansion valve;
6. Replace the outdoor control
board.
14
T
he high pressure
switch operat
ion
or
the unit
is
turn
ed
off
for high pressure
protection
1.
2.
The wiring of the high pressure
protector
is
connect
ed
loose
ly
;
The high pressure protector
fails;
3.The outdoor control board is
abnormal;
4. Overload in cooling;
5. Overload in heating.
1.
2.
Reconnect the wiring
of
the
high
pressure protector;
Replace the high pressure
protector;
3.
Replace the outdoor control
board;
4.
Please refer to
N
OTE
3;
5.
Please refer to
N
OTE
4.
Applied to
models with
high
pressure
switch or
pressure
sensor
15
T
he low pressure
switch protection or
the unit
is
turn
ed
off
for low pressure
protection
1.
The wiring of the low pressure
switch
is
connect
ed
loose
ly
;
2.
The low pressure switch fail
s
;
3.
The refrigerant is not enough;
4.
The expansion valve fail
s
in
heating mode;
5.
The outdoor control board is
abnormal.
1.
Reconnect the wiring of the
low pressure switch;
2.
Replace the low pressure
switch;
3.
Check the welding point to
confirm whether the unit
leaks
,
and add some refrigerant;
4.
Replace the expansion valve;
5.
Replace the outdoor control
board.
Applied to
models with
low pressure
switch or
pressure
sensor
16
O
verload protection
in cooling mode
System overload
Please refer to
N
OTE
3.
17
Discharge
temperature sensor
fault
1.
The wiring of the discharge
tempe
-r
ature sensor
is
connect
ed
loose
ly
;
2. The discharge temperature
sensor fails;
3.The sampling circuit is abnormal.
1. Reconnect the wiring of the
discharge temperature sensor;
2. Replace the discharge
temperature sensor;
3. Replace the outdoor control
board.
18 AC voltage is
abnormal
1.
The AC voltage>275V or <160V
;
2.
The AC voltage of sampling circuit
on the driver board is abnormal
.
1.
Normal protection, please
check the supply power;
2.
Replace the driver board.
19 Suction temperature
sensor fault
1.
The wiring of the suction
tempe
-
r
ature sensor
is
connect
ed
loose
ly
;
2.
The suction temperature sensor
fail
s
;
3.
The sampling circuit is abnormal
.
1.Reconnect the wiring of the
suction temperature sensor;
2.Replace the suction
temperature sensor;
3.Replace the outdoor control
board.
22 The defrosting sensor
fault
1.
The wiring of the defrosting sensor
is
connect
ed
loose
ly
;
2.
The defrosting sensor fail
s
;
3.
The sampling circuit is abnormal
.
1. Reconnect the wiring of the
defrosting sensor;
2. Replace the defrosting sensor;
3. Replace the outdoor control
board.
45 IPM fault
There are many reasons for this
failure
.
You can check the driver
board
fault
LED to
further
a
naly
ze
the fault code of the drive board and
to learn about what leads to the fault
and how to operate it
. Specific
information can be
see
n in
table 5,
table 6.
See attached "analysis of the
driving board fault".
-
3
8
-
Summary of Contents for WHU09DHA21S
Page 57: ...2 3 4 5 6 7 8 9 10 11 1 Indoor unit WHU09DHA21S 56 Parts list ...
Page 58: ...12 13 14 15 16 17 18 19 14 15 57 Fan ...
Page 59: ...20 21 22 58 Electrical parts ...
Page 61: ...2 3 4 5 6 7 8 9 10 11 1 60 Indoor unit WHU12DHA21S ...
Page 62: ...12 13 15 16 17 18 19 14 14 15 61 Fan ...
Page 63: ...20 21 22 62 Electrical parts ...
Page 65: ... 64 Indoor unit WHU18DHA21S 2 3 4 5 6 7 8 9 10 11 1 ...
Page 66: ... 65 Fan 12 13 16 17 18 19 20 21 22 14 14 14 15 15 15 ...
Page 67: ... 66 Electrical parts 23 24 25 ...
Page 69: ...Indoor unit WHU24DHA21S 68 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 ...
Page 70: ... 69 Fan 16 17 18 19 20 21 22 23 18 23 ...
Page 71: ... 70 Electrical parts 24 25 26 27 25 ...
Page 73: ...Indoor unit WHU36DHA21S 72 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 1 ...
Page 74: ... 73 Fan 20 21 22 23 24 25 26 27 22 24 25 27 ...
Page 75: ... 74 Electrical parts 28 29 30 29 31 ...
Page 77: ...Outdoor unit WHU09SZA21S 76 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 ...
Page 78: ... Refrigerant cycle 77 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 ...
Page 79: ... Electrical parts 78 32 33 34 35 36 37 38 39 40 31 41 ...
Page 81: ...Outdoor unit WHU12SZA21S 80 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 ...
Page 82: ... Refrigerant cycle 81 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 ...
Page 83: ... Electrical parts 82 32 33 34 35 36 37 38 39 40 31 41 ...
Page 85: ...Outdoor unit WHU18SZA21S 84 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 ...
Page 86: ... Refrigerant cycle 85 17 18 19 20 21 22 23 24 25 26 27 28 29 30 35 31 34 48 32 33 ...
Page 87: ... Electrical parts 86 36 37 38 39 40 41 42 43 45 46 47 44 ...
Page 89: ...Outdoor unit WHU24SZA21S 88 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 1 ...
Page 90: ... Refrigerant cycle 22 23 24 25 26 27 28 29 30 32 33 34 35 36 31 89 37 ...
Page 91: ... Electrical parts 90 38 39 40 42 43 44 45 46 47 48 49 41 ...
Page 93: ...Outdoor unit WHU36SZA21S 92 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 ...
Page 94: ... Refrigerant cycle 93 17 18 19 20 21 22 23 24 25 26 27 28 29 30 32 33 31 ...
Page 95: ... Electrical parts 94 34 35 36 37 38 39 40 42 43 44 45 46 47 48 49 41 ...