14 | Westinghouse Portable Power

No Connected Loads

 – Make sure the generator has no 

connected loads before starting it. To ensure there are no 

connected loads, unplug any electrical extension cords that 

are plugged into the control panel receptacles.

NOTICE

Starting the generator with loads already applied to it could result in 

damage to any appliance being powered off the generator during the 

brief start-up period.

Grounding the Generator

 – The National Electric Code 

(NEC), as well as many local electrical codes, may require 

the generator to be connected to earth ground. The most 

common application that requires a ground rod is when you 

are using the generator as a separately derived system to 

provide back up power to your house. Typically this is when a 

transfer switch has a switched neutral.

As the generator application has many variables that cannot 

be determined by the manufacturer of the generator, a 

licensed electrician will need to determine if a grounding rod is 

needed. 

If a licensed electrician has determine the application requires 

a ground rod, make sure it is connected to earth ground by 

connecting the ground terminal on the control panel to earth 

ground using copper wire (minimum 10 AWG). Consult a 

qualified electrician for local grounding requirements.

Neutral Bonded: There is a permanent conduct or between 

the generator (stator winding) and the frame.

WARNING

Be sure the generator is properly connected to 

earth ground before operating. The generator 

must be grounded to prevent electrical shock 

due to faulty appliances.

 
High Altitude Operation

Engine power is reduced the higher you operate above sea 

level. Output will be reduced approximately 3.5% for every 

1000ft of increased altitude from sea level. This is a natural 

occurrence and cannot be adjusted by engine. Increased 

exhaust emissions can also result due to increased fuel 

mixture. Other issues include hard starting, increased fuel 

consumption and spark plug fouling. Contact our service 

team 

1-855-944-3571

 for altitude part kits.

High Altitude Carburetor Kit Part Number: 140545

BEFORE STARTING THE GENERATOR

BEFORE STARTING THE GENERATOR, 

REVIEW SAFETY SECTION STARTING ON 

PAGE 5.

Location Selection

 – Before starting the generator, avoid 

exhaust and location hazards by verifying:

• 

You have selected a location to operate the generator 

that is outdoors and well ventilated.

• 

You have selected a location with a level and solid 

surface on which to place the generator.

• 

You have selected a location that is at least 15 feet 

(4.5 m) away from any building, other equipment or 

combustible material.

• 

If the generator is located close to a building, make 

sure it is not located near any windows, doors and/or 

vents.

WARNING

Always operate the generator on a level surface. 

Placing the generator on non level surfaces can 

cause the generator to tip over, causing fuel and 

oil to spill. Spilled fuel can ignite if it comes in 

contact with an ignition source such as a very hot 

surface.

NOTICE

Only operate the generator on a solid, level surface. Operating the 

generator on a surface with loose material such as sand or grass 

clippings can cause debris to be ingested by the generator that 

could:

• Block cooling vents

• Block air intake system

 

Weather

 – Never operate your generator outdoors during 

rain, snow or any combination of weather conditions that 

could lead to moisture collecting on, in or around the 

generator.

Dry Surface

 – Always operate the generator on a dry 

surface free of any moisture.

OPERATION 

Summary of Contents for WGen5500

Page 1: ...USER MANUAL WGen5500 Portable Generator 5500 Running Watts 6850 Peak Watts...

Page 2: ...to be seriously hurt or killed Model Number Running Watts Peak Watts Fuel Tank Size L G Rated Speed RPM Ignition Type Spark plug Engine Disp cc Stroke X Bore Oil Capacity L Oil Type THD WGen5500 5500...

Page 3: ..._ Model Number ______________________________________ Last Name ________________________________________ Serial Number _______________________________________ Street Address __________________________...

Page 4: ...ns 16 How to Float the Neutral Ground 16 Engine Fluids and Fuel 16 Adding Gasoline to the Fuel Tank 17 Power Output and Demand 18 Starting the Generator 18 Manual Start 18 Stopping the Generator 19 No...

Page 5: ...ot avoided could result in death or serious injury CAUTION Indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE Indicates a situation which can cause da...

Page 6: ...Never remove the fuel cap with the engine running Never refuel the generator while the engine is running Always turn engine off and allow the generator to cool before refueling Only fill fuel tank wit...

Page 7: ...Chine CSA Master Contract Number Num ro de contrat principa l de CSA MWE Investments LLC Columbus Ohio 43228 USA Con u columbus Ohio tats Unis MWE Investments LLC Columbus Ohio 43228 Etats Unis Part N...

Page 8: ...8 Westinghouse Portable Power SAFETY SAFETY LABELS AND DECALS 8 9 7 10 8 9 6 6 7 5 10...

Page 9: ...ld back top flaps to reveal the manual 3 Remove the Wheel Kit Accessories cardboard box 4 Carefully cut two sides of the carton to remove the generator WHAT COMES IN THE BOX Manual Quick Start Guide M...

Page 10: ...wheel kit is not intended for on road use The wheel kit is designed for use on this generator only INSTALLING FEET TO FRAME 1 Place generator on a flat surface 2 Place a piece of cardboard or other s...

Page 11: ...nd outlets Oil Fill Plug Dipstick Must be removed to add and check oil Oil Drain Plug Must be removed to drain engine oil Never Flat Wheels For easy portability Fuel Shut off Valve Controls the flow o...

Page 12: ...the spark plug CARB Canister Required for models sold into and used in California Muffler and Spark Arrester Avoid contact until engine is cooled down Spark arrestor prevents sparks from exiting the m...

Page 13: ...Control Switch Allows fuel to flow to engine and energizes the ignition system Data Center The VFT Meter is an LED display that will rotate through volts frequency and lifetime run hours You can press...

Page 14: ...utput will be reduced approximately 3 5 for every 1000ft of increased altitude from sea level This is a natural occurrence and cannot be adjusted by engine Increased exhaust emissions can also result...

Page 15: ...n the top line of the chart Then select the rated amperage of the generator on the left side of the chart Where the two meet is the size of the conductor required for the application When using the WC...

Page 16: ...intained during the operation of the generator Failure to maintain the proper oil level can result in engine damage OPERATION CONNECTING THE GENERATOR TO A BUILDING ELECTRICAL SYSTEM It is recommended...

Page 17: ...ne is filled with engine oil See Checking Engine Oil on page 22 The generator is situated in a proper location Location Selection on page 14 The generator is on a dry surface Weather and Dry Surface o...

Page 18: ...eld or portable devices and a value of 3 5 for larger stationary devices For example a 900 W angle grinder can be assumed to have a starting power demand of at least 1 2 900 W which equals 1 080 W Sim...

Page 19: ...Normal Operation During normal operation use the following steps to stop your generator 1 Remove any connected loads from the control panel receptacles 2 Allow the generator to run at no load to redu...

Page 20: ...tor to malfunction and could result in death or serious injury NOTICE Periodic maintenance intervals vary depending on generator operating conditions Operating the generator under severe conditions su...

Page 21: ...muffler cover 4 Once the cover is removed locate the screw on the tip of the muffler and remove Pull the spark arrestor out of the muffler see Figure 15 Figure 15 Remove spark arrestor 5 If the spark...

Page 22: ...Figure 18 below Figure 18 Oil Fill Plug Dipstick 6 Check oil level When checking the engine oil remove the oil fill plug dipstick and wipe it clean Thread the oil fill plug dipstick all the way back i...

Page 23: ...apply slow but firm squeezing action 6 Rinse in clean water by submerging the air filter elements in fresh water and applying a slow squeezing action CHANGING ENGINE OIL 1 Always operate or maintain t...

Page 24: ...ug boot by firmly pulling the plastic spark plug boot handle directly away from the engine see Figure 23 NOTICE Never apply any side load or move the spark plug laterally when removing the spark plug...

Page 25: ...o loosen and remove all dirt on or around the engine s cooling fins Clean All Alternator Cooling Air Inlets and Exhaust Ports Make sure the cooling air inlets and exhaust ports of the alternator are f...

Page 26: ...an come in contact with an ignition source such as a 1 pilot light of a stove water heater clothes dryer or any other gas appliance or 2 spark from an electric appliance NOTICE Gasoline stored for as...

Page 27: ...ugged spark arrestor 9 Check and clean the spark arrestor 10 Stale fuel 10 Drain fuel and replace with fresh fuel 11 If trying 1 11 above does not solve the problem the cause might be the generator ha...

Page 28: ...enerator Accessories call to order 210004 GENERATOR COVER 210003 WGC25 25 POWER CORD 210052 30A 6 BREAKER TRANSFER SWITCH KIT MODEL WHMTS30 210075 25 Cord 30AMP Transfer Switch 210076 50A 6 BREAKER TR...

Page 29: ...IRE WGen5500 EXPLODED VIEW PART NO No Part Description 1 100533 FRAME 2 100552 ISOLATOR B 3 100553 ISOLATOR A 4 100551 NUT M10 5 180524 NUT M8 6 150507 CONNECTING PIPE 7 180563 BRACKET AIR CLEANER 8 1...

Page 30: ...190418 CRANKCASE 2 180536 BALL BEARING 3 180504 OIL SEAL 4 190225 GOVERNOR ASSEMBLY 5 190410 SHAFT GOVERNOR ARM 6 190409 WASHER GOVERNOR ARM SHAFT 7 190408 PIN LOCK 8 180507 BOLT DRAIN PLUG 9 180508 W...

Page 31: ...EL PIN CASE COVER 13 190407 PISTON 14 190406 PISTON RING SET 15 190405 ROD ASSEMBLY CONNECTING 16 190404 PIN PISTON 17 180791 CLIP PISTON 18 180534 COVER ASSEMBLY CRANKCASE 19 170502 CLIP 20 190417 CY...

Page 32: ...32 Westinghouse Portable Power WGen5500 SCHEMATIC...

Page 33: ...6 gal 25 L Run Time at 25 Load hrs 20 hrs Run Time at 50 Load hrs 15 hrs Gasoline Fuel Gauge Yes Choke type Manual Choke Location Above Air Filter AC Outlets 1 120 240V 30A L14 30R 2 Duplex 120V 20A G...

Page 34: ...34 Westinghouse Portable Power Version 07 23 18KD...

Reviews: