WHL-033 Rev. 1.29.16
44
ENTER MENU CODE
000
C. Operating Instructions
Before operating the unit, it is important to remove the cover
and verify that the gas line and water lines are connected to
boiler and fully purged. If you smell gas, STOP; Follow the safety
instructions listed in the first part of this section. If you do not
smell gas, follow the next steps.
1. Turn down the thermostats before applying power to the
boiler. If 0–10 volt or other inputs are used, make sure that they
are set so there is no call for heat while programming.
2. Turn on the power to the boiler or boilers if a cascade system
used.
3. Next, check the boiler settings. Adjustment and factory
defaults are outlined within this section. If a cascade system is
used, it is important that all the boilers have the same boiler
settings.
4. Next, check the system settings. Adjustments and factory
defaults are outlined within this section. If a cascade system is
used, it is important that the Master Boiler is programmed with
the correct system settings.
5. Create a demand on the boiler or boilers if a cascade system
is used. The user can monitor system functions when the boilers
are operational.
6. If the boilers fail to start, refer to the troubleshooting section
in the back of this manual.
D. Programming Boiler Settings
Boiler Setting Program Access
Note: Programming the boiler control is not possible when
the boiler is firing. Make sure any input which can create a
demand on the boiler, such as the tank thermostat, is turned
off, so the boiler will remain idle to allow programming.
Screen
Description
ENTER MENU CODE
000
To access the boiler setting program,
press and hold
ENTER
for 4 seconds
until the display shows the screen at
left.
ENTER MENU CODE
600
Use the arrow keys to log in the
Boiler
Menu Access Code - 600
. Press
ENTER
to confirm the code and access the
Boiler Setting Program
navigation
menu.
Table 13 - Boiler Setting Access
Boiler Setting Program Navigation
Once the code is confirmed, the user can start to set the
Boiler Settings
. Use the arrow keys on the display to navigate
through the
Boiler Settings
. A blinking setting indicates the
setting can be changed. To change a setting, press
ENTER
.
Boiler settings can be increased by pressing
^
and decreased
by pressing
v
on the display. When done, press
ENTER
. The
setting will stop blinking and the user can move on to next
setting. Press
RESET
to exit programming and store settings.
Listed below are the boiler settings that can be programmed
into the control.
Screen
Description
CENTRAL HEAT
180
o
F
Allows the user to adjust the boiler
set point from 50F to 190
o
F (Factory
Default 180
o
F).
CENTRAL DIFF SET
30
o
F
Adjusts the boiler differential set point
from 5
o
F to 30
o
F (Factory Default 30
o
F).
DHW SETPOINT
119
o
F
Adjusts the indirect tank set point from
70
o
F to 185
o
F (Factory Default 119
o
F).
DHW DIFF SETPOINT
7
o
F
Adjusts the DHW differential set point
from 1
o
F to 30
o
F (Factory Default 7
o
F).
TEMP DISPLAY C OR F
o
F
Adjusts
the
temperature
measurement in F = Fahrenheit to
C = Celsius (Default is Fahrenheit).
Table 14 - Boiler Setting Program Navigation
RESET
– The RESET button has two functions.
– Resets any lockout error code
– Returns the user to the default display screen.
ENTER
– The ENTER key is used to access parameter
programming mode. To access this mode, hold down the ENTER
key for more than 4 seconds. The readout will change to:
One of the zeroes will be blinking. Use the
^ v
arrow keys to
change the blinking digit to the correct value. Use the
< >
arrow
keys to select the next digit to change and again use the
^ v
keys
to change the value. Repeat until the correct code is entered.
Press the
ENTER
key to accept the code entered. If the code is
correct, the readout will change to the appropriate screen. If the
programming code is not accepted, the readout will continue to
display as shown above.
ENTER
is also used to enable a function for editing. After the
user navigates to the desired function, the user holds down
ENTER
for one second. When
ENTER
is released, the function
value will begin to blink. The function can now be changed
using the
^ v
keys. After the new value is displayed, the user
then presses
ENTER
for 1 second to lock the new value of the
function. The value will then stop blinking.
LEFT AND RIGHT ARROW KEYS
–
< >
are used to navigate
between the default display, status display, analog and
cascade displays if they are enabled. The
< >
keys are also used
in programming modes to change between programmable
functions. It is recommended you use the Menu Maps in the
back of this manual and the detailed menu instructions printed
in this section to help in menu navigation.
UP AND DOWN ARROW KEYS
–
^ v
are used to navigate
between the various functions displayed in the menu. After the
function is enabled for editing by pushing the
ENTER
key, the
^
v
keys are used to adjust the function upward or downward to
the desired value.
Clock Settings
(
NOTE:
The clock will reset if the boiler is powered off for
more than a week.)
Screen
Description
CLOCK MODE (12/24)
08/28/2009 Fr 9:42A
Changes the clock from 12 hour
mode (8:45 PM) to 24 hour mode
(20:45). To change to 24 hour mode,
press
ENTER
. The letter (A or P)
after the time will blink. Press the
up or down arrow key once and the
letter will disappear. Press
ENTER
to
save the new setting.
CLOCK HOUR
08/28/2009 Fr 10:01A
Allows the user to adjust the hour
setting.
Summary of Contents for WBMC**500
Page 36: ...WHL 033 Rev 1 29 16 36 Figure 27 Internal Connection Diagram ...
Page 59: ...WHL 033 Rev 1 29 16 59 Figure 32 500 Combustion System Replacement Parts Model ...
Page 60: ...WHL 033 Rev 1 29 16 60 Figure 33 850 Combustion System Replacement Parts Model ...
Page 61: ...WHL 033 Rev 1 29 16 61 Figure 34 Water Side Replacement Parts All Models ...
Page 62: ...WHL 033 Rev 1 29 16 62 Figure 35 Cabinet Replacement Parts All Models ...