background image

The  voltage  at  which  the  contact  picks  up  can  be 
varied  by  means  of  the  adjustable  resistor.  The 

time  for  the  moving  contact  to  r eset  to  the  right  hand 

stationary  contact  may  be  delayed  for  a  minimum  o f  

cycles  (see  section  under  "SETTINGS"). 

Indicating  Contactor  Switch  Unit  (ICS) 

The  indicating  contactor  switch  is  a  small  d-e 
operated  clapper  type  device.  A  magnetic  armature, 

to  which  leaf-spring  mounted  contacts  are  attached, 

is  attracted  to  the  magnetic  core  upon  energization 
of  the  switch.  When  the  switch  closes,  the  moving 
contacts  bridge  two  stationary  contacts,  completing 
the  trip  circuit.  Also  during  this  operation  two 
fingers  on  the  armature  deflect  a  spring  located  on 
the  front  of  the  switch,  which  allows  the  operation 

indicator  target  to  drop.  The  target  is  reset  from  the 

outside  of  the  case  by  a  push  rod  located  at  the 
bottom  of  the  cover. 

The  front  spring,  in  addition  to  holding  the  target, 

provide  restraint  for  the  armature  and  thus  controls 
the  pickup  value  of  the  switch. 

Contacts 

The  moving  contact  assembly  in  the  overvoltage 

unit  has  been  factory  adjusted  for  low  contact 
bounce  performance  and  should  not  be  disturbed. 

SE TTINGS 

Overvoltage Unit 

(V) 

The  only  setting  required  is  the  pickup  voltage 

setting  which  is  made  by  means  of  the  adjustable 

resistor.  Increasing  the  resistance  will  increase 

the  pickup  voltage. 

For  the 

15-45 

volt  unit,  the  relay  as  received  has 

been  factory  adjusted  to  pick  up  at  the  high  end  of 
the  pickup  range.  Pickup  at  the  low  end  of  the 
range  can  be  achieved  by  merely  shorting  out  the 
resistor. 

The 

108- 132 

volt  unit  can  be  adjusted  from 

108 

to 

132 

volts  by  adjusting  the  resistor,  and  is  normally 

set  for 

108 

volts  at  the  factory. 

The  contact  gap  is  factory  adjusted  for 

.020". 

If 

cycle  minimum  reset  time  is  desired  simply  back 

off  the  left-hand  station  contact  until  the  moving 

contact  does  not  make  in  the  picked  up  position. 

INSTALLATION 

The  relays  should  be  mounted  on  switchboard  panels 

or  their  equivalent  in  a  location  free  from  dirt, 

moisture,  excessive  vibration,  and  heat.  Mount  the 

relays  vertically  by  means  of  the  four  mounting 

holes  on  the  flange  for  semi-flush  mounting  or  by 
means  of  the  rear  mounting  stud  or  studs  for  pro­
jection  mounting.  Either  a  mounting  stud  or  the 

mounting  screws  may  be  utilized  for  grounding  the 

relay.  The  electrical  connections  may  be  made 

directly  to  the  terminals  by  means  of  screws  for 
steel  panel  mounting  or  the  terminal  studs  furnished 

with  the  relay  for  thick  panel  mounting.  The  ter­
minal  studs  may  be  easily  removed  or  inserted  by 
locking  two  nuts  on  the  stud  and  then  turning  the 

proper  nut  with  a  wrench. 

AD 

US T ME N T S 

M A I NT E N  AN CE 

The  proper  adjustments·  to  insure  correct  operation 

of  this  relay  have  been  made  at  the  factory.  Upon 

receipt  of  the  relay,  no  adjustments,  other  than 

those 

covered  under 

"SETTINGS," 

should  be 

required. 

Overvoltage  Unit 

(V) 

1. 

Contact  Gap- The  gap  between  the  left-hand 

stationary  and  moving  contacts  with  the  relay  in 

the  de-energized  position  should  be  approxi­
mately 

.020". 

2. 

For  the 

15-45 

volt  unit,  the  pickup  of  the  over 

voltage  unit  can  be  checked  by  increasing  the 

voltage  to  the  relay  to 

45 

volts. The  relay  should 

pickup  within 

± 

5% 

of  this  value.  The 

15 

volt 

pickup  can  be  checked  by  shorting  the  resistor 
and  increasing  the  voltage  to  this  value.  The 

relay  should  pickup  within 

± 

5% 

of 

15 

volts. 

3. 

For  the 

108- 132 

volt  unit,  the  relay  can  be 

adjusted  to  pickup  anywhere  within  this  range 
with  a  resistor  adjustment. 

Indicating  Contactor  Switch  (ICS) 

Close  the  main  relay  contacts  and  pass  sufficient 

d-e  current  through  the  trip  circuit  to  close  the 

contacts  of  the 

res. 

This  value  of  current  should 

be  between 

and 

1.2 

amperes.  The  indicator 

should  drop  freely. 

The  contact  gap  should  be  approximately 

5/64" 

between  the  bridging  moving  contact  and  the  ad­

justable  stationary  contacts.  The  bridging  moving 

contact  should 

touch  both  stationary  contacts 

simultaneously. 

ROUTINE  MAINTE NANC E 

All  relays  should  be  inspected  periodically  and  the 

operation  should  be  checked  at  least  once  every 

year  or  at  such  other  time  intervals  as  may  be 

dictated  by  experience  to  be  suitable  to  the  par­

ticular  application. 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for KV-1

Page 1: ...feed terminal In this case the trip units are supervised by the type KA carrier auxiliary relay to prevent tripping for external faults Hot line reclosing is another application for this relay CONSTRU...

Page 2: ...oving contact arm by a spiral spring The spring adjuster is also held in place by a spring type clamp With the contacts closed the electrical connection is made through the stattionary contact housing...

Page 3: ...or optimum follow and this adjustment should not be disturbed SETTINGS The relay as received has been factory adjusted for 100 volt dropout Any other dropout voltage over the range can be gotten by va...

Page 4: ...adjustments other than those covered under SETTINGS should be required Accept e_ _Check The following check is recommended to insure that the relay is in proper working order 1 Contact Gap ThP contact...

Page 5: ...ure should not be used unless it is apparent that the relay is not in proper working order See Acceptance Check Undervoltage Unit V 1 The upper pin bearing should be screwed down until there is approx...

Page 6: ...til the moving contact just makes with the right hand stationary contact Indicating Contactor Switc ICS Adjust the contact gap for approximately 5 64 1 64 0 Close the main relay contacts and check to...

Page 7: ...EST JACK TERMINAL 185A336 Fig 1 Internal Schematic 0 z 0 ILl _ J I LI 1 50 45 40 35 30 25 20 15 10 5 0 0 J j 1 I v v v v v n l l v 80 V DROPOUT SETTING 100 V DROPOUT SETTING 10 20 30 40 50 60 70 80 90...

Page 8: ...12 MTI ICIEWI 12 y I J PAIIEL COUTOUT I DltU t FOI ISU FWIII Mrl PAIIEI Dill U IK8 011 CUTClll fOit I ROJECTIOII Mh fiOIT YlEW 57 D 7901 Fig 3 Outline and Drilling Type FT 21 Case WESTINGHOUSE ELECTRI...

Page 9: ...ary without having to remove the magnetic core from the frame The electromagnet has two pairs of coils The coils of each pair are mounted diametrically opposite one another In addition there are two l...

Page 10: ...irt moisture excessive vibration and heat Mount the relays vertically by means of the four mounting holes on the flange for semi flush mounting or by means of the rear mounting stud or studs for pro j...

Page 11: ...ionary contact in position With the resistor shorted out pass 15 volts a c through the relay terminals The sensitivity adjustment is made by varying the tension of the spiral spring attached to the mo...

Page 12: ...IC ICS 9 9 9 __Q__ Q___ _____ _ 0 0 0 FRONT VIEW Fig 7 Internal Schematic VARISTOR ltWICATINu COtHACTOR SwiTCti iJOLTA iE UNIT RED HANDLE TEST SWITCt1 TERMI1 AL 184A262 w w w E l e c t r i c a l P a r...

Page 13: ...J a 0 10 5 0 TYPICAL OPERATE TIME CURVES r CONTACT CLOSING L 1 v C NTACT OPENING J 0 2 4 6 8 10 12 14 16 18 20 MULTIPLES OF PICKUP VOLTAGE Fig 2 Typical Operate Time Curves I L 41 933 18 3494A53 5 w w...

Page 14: ...H MTG PANEL CUTOUTS DRILLING PROJEC TION MTG FOR SEMI FLUSH MTG 1 344 SPACERS FOR 34 14 THIN PANELS 5 16 18 SCREW FOR THICK PANELS 594 USE 5 16 18 STUDS J 5 og I DIA 2 HOLES 250 g l6 39 _ 6 35 375 1 0...

Page 15: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 16: ...WESTINGHOUSE ELECTRIC CORPORATION RELAY INSTRUMENT DIVISION NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Reviews: