D I R ECTI ONAL OVERCU RR ENT GROUND R E LAYS
R E LAY TY P E
KRP
KRD (Voltage
Unit)
KRC
KRD (Current
Unit)
T AB L E I
D I R ECTIONAL UNIT SENSITIVITY
AMP ER E RATI NG
VAL UES FOR M I N . P I CK U P
T
VOLTS
AMP E R ES
. 5-2
1-4
1
2 . 0
2-8
1
4 . 0
4- 1 6
1
4 . 0
1 0-40
1
8.0
.
5
-
2
0
.
5
1-4
2-8
*
0 . 57
4- 1 6
1 . 0
1 0-40
* 1 . 4
T
The en ergi zation quantitie s are input quantitie s at the relay tenninal s.
TT
M aximum torque angl e.
TAB L E I I
DI R ECTIONAL U N I T CAL I B RATI O N
R ELAY RAT I NG
CUR R E NT AMP E R ES
BOT H PLUGS I N COND I T I ON
All Ranges
80
Spurious Torque In Contact
Closing Direction ( Left Front
View)
All
Ranges
80
Spurio us Torque In Contact
Opening Direction (Right Front
View) (Contacts remain open)
PHAS E ANG L E RE LAT I ONSH I P
I lagging V by
60°
TT
I in-phase with V
I lagging V by
60°
TT
I in-phase with V
1a
leading
�
by
40°
TT
In-phase
1a
leading
by
40°
TT
ADJ USTM E NT
Right (Front-View) Plug Screwed
Out Until Spurious Torque is Re-
versed.
Left (Front View)
Plug
Screwed
Out Until Spurious Torque is in
Contact Closing Direction. Then
the plug is screwed in Until Spuri-
ous Torque is Reversed.
Short circuit the voltage polarizing circuit and open circuit the current pol arizin g circuit at the relay tenninal s
before making the above adjustments.
14
www
. ElectricalPartManuals
. com
Summary of Contents for KRD-4
Page 27: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 108: ... w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 110: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 112: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 114: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...