may be desired on some installations in order tO in
sure that the relay will always trip the breaker on
zero potehtiaL
Ind i cat i n g Contactor Swi tch ( I CS)
Adjust the contact gap for approximately
5/64 "
( - 1/ 64 " , +0).
Close the main relay contacts and check to see
that the relay picks up and the target drops between
1
and
1 . 2
amperes d-e.
To increase the pickup current remove the molded
cover and bend the springs out or away from the cover.
To decrease the pickup current bend the springs
in
toward the cover.
R E N E W A L P A R T S
Repair work can be done most satisfactorily at
the factory. However, interchangeable parts can be
furnished to the customers who are equipped for
doing repair work. When ordering parts, always give
the complete nameplate data.
RATING OF OVERCURRENT UNIT
RANGE
. 5-2
1-4
2-8
4- 1 6
HHO
CONTI NUOUS RAT I NG AMP E R ES
5
8
8
10
10
ONE SECOND R AT I NG AMP E R E S
100
140
140
200
200
l3
www
. ElectricalPartManuals
. com
Summary of Contents for KRD-4
Page 27: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 108: ... w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 110: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 112: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 114: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...