l
MOVING
RELAY MOLD
STOP SURFACE
COVER
159
COIL
S TATIONARY CONT. L.P.
160
R.P.
165
LOCATION
I
I
I
I
I 1 I
I
I I
I
I
I
r--------+
1
I
I
RELEASE
LEVER
1
R E LA
RELEASE ARM
DETAILS
161
RELEASE
LEVER
ARC CHUTE FOR D-C ONLY
FIG.
9.
Control Relay-Location, Adjustment, and Construction Details
4.
Remove the operating mechanism from the
platform and (a) remove and discard the molded
trip fingers from the trip bar; (b) remove and dis
card the bras� counterbalance from the bottom of
the trip lever. Remount the operating mechanism.
5.
If the breaker is equipped with a shunt trip at
tachment, remove a:n:d discard the trip lever from the
shunt trip and replace with trip lever Slit 1736189.
6. If
the breaker is equipped with an electric lock
out attachment remove and discard the
1;16
thick
Micarta angle screwed to the electric lockout
lift
ing plate. Insulation is not required with the in
sulated overcurrent device.
7.
Loosen the control relay and solenoid mount
ing bolts on DB-15 breakers
(if
supplied) and tilt
forwards slightly to permit easy installation of the
23
www
. ElectricalPartManuals
. com
Summary of Contents for De-ion DB-15
Page 24: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 27: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 29: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 31: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 33: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 35: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 37: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 39: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 41: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 43: ... w w w E l e c t r i c a l P a r t M a n u a l s c o m ...