Type 50-DH-50 Air Circuit Breaker 

600-1200 Amperes, 

5000 Volts 

PURPOSE 

The  purpose  of  this  instruction  book  i� 

!O 

ac­

quaint  the  recipient  with  the  characten�t1cs  of 

the· 50-DH-50  Air  Circuit  Breaker.  Thts  book 

voids the Advance Instruction Book I.  B. 

33-670-2 

printed 

6-43. 

Instructions necessar�  for  the  co�­

plete  installation  operation  and  mamtenance  wtll 

be  found· betwee

� 

the  covers  of  this  book.  The 

type DH Air Circuit Breaker  is  rather  new,  how-

ever,  its operation is,  to a considerable degree,  simi­

lar to that of an oil circuit breaker.  It is built by a 

company  that  has  been active in the manufacture 

of the higher voltage power air circuit breakers for 

the past fifteen years. 

Fundamentally  a  power circuit  breaker  is  a  de­

vice  for  interrupting  a  circuit  between  separable 

contacts  under  normal  or  abnormal  conditions. 

Ordinarily  circuit breakers are required to operate 

only infrequently although  some  classes  of  break­

ers are suitable for frequent operations.  The  type 

"DH  De-ion"  Air  Circuit  Breaker  is  designed  to 

operate in a normal atmosphere and is not depend­

ent  on  the  maintenance  of  any  stored  medium, 

such  as  air or liquid dielectric.  Its performance  is 

dependable,  clean-cut  and  free  from  uncertainty. 

Fig. 

2-Type 50-DH-50,  600 Ampere, 5000 Volt, 3-Po!e-, "De­

Fig. 

1-

Type 50-DH-50,  600 Ampere,  5000 Volt, 3-Pole,  "De-

ion"  Air  Circuit  Breaker. 

Inter-phase  Barrier  and 

Arc 

ion"  Air  Circuit  Breaker. 

Chamber  Removed 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for 50-DG-50

Page 1: ...s 5000 Volts Installation Operation Maintenance INSTRUCTION BOOK CAUTIONS Safety for Personnel Storage Handling Unloading Unpacking Page 6 7 7 Westinghouse Electric Corporation East Pittsburgh Pa I B 32 130 lB w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 2: ...ower air circuit breakers for the past fifteen years Fundamentally a power circuit breaker is a de vice for interrupting a circuit between separable contacts under normal or abnormal conditions Ordinarily circuit breakers are required to operate only infrequently although some classes of break ers are suitable for frequent operations The type DH De ion Air Circuit Breaker is designed to operate in...

Page 3: ...a vertical plate is attached This vertical plate supports the bushings contacts magnetic circuits and arc chambers all of these parts being at high potential Operating Mechanism The electrical operatingmechanismsupplied with this breaker is the direct current solenoid type SAF 2 slightly modified to be adaptable to the ap plication involved This mechanism is mounted so that the moving core operati...

Page 4: ...ned to the top of and project over the stationary main tongues so that they engage the arcing contact surface on the blades as the breaker is opening or closing how ever these arcing contact surfaces do not engage each other when the breaker is in the fully closed position The entire contact arrangement is so de signed that the arcing contacts which have arc resisting surfaces part last on opening...

Page 5: ...t Strap Arcing Secondary Moving Contact Arm Contact Platform Arcing Contact Fig 6 Typical Arrangement of Component Parts 6 to the lower breaker terminal thus relieving the contacts of the current carrying duty until the arc is extinguished in slot of the arc chamber 5 6 SAFETY FOR PERSONNEL The installation operation and maintenance of circuit breaker equipment requires that certain pre cautionary...

Page 6: ...after they have 7 first been made snug In later models the upper cup washer has been replaced with a conical spring and spacer arrangement in which case the nut should be turned up tight on the spacer and cottered in that position When adjusted in this manner the moving contact blades will separate approximately h inch when the arcing contacts engage There should be a slight clearance between the ...

Page 7: ...cumulated in the air line will not be sprayed over insulating surfaces Direct the air stream thoroughly into all joints and crevices If com pressed air is not available this cleaning may be done with a clean dry cloth Steam waste is not recommended for this purpose because of its tend ency to leave a residue of lint on insulating surfaces 8 Magnetic Circuit The magnetic circuit assembly consists o...

Page 8: ...G L V R SPRING TOP PLAT MOVING COR PUSH R O D B OTTOM PLAT MOVING COR SUPP ORT COR GU I D TUB Fig 7 Type 50 DH 50 Electrical Operating Mechanism AUXILIARY SWITCH ARM OPERATING COUNTER OPERATI ON COUNTER ARt l AND CLOSING L V R RIP ATTACtiM NT MOUNTING BOLT UXILIARY SWITCH INGLE COIL HUNT TRIP t J 0 b i a E l e c t r i c a l P a r t M a n u a l s c ...

Page 9: ...uipped with a Rectox unit on alternating current It is a mechanically full automatic mechanism and is trip free in all positions An electrical closing operation 10 is secured by energizing the closing coil A magnetic flux generated by the closing coil forces the moving core and attached push rod upwards against the push rod roller located at the junction of the breaker lever links and the mechanis...

Page 10: ...erload continues an oil dashpot delaying device is attached to the end of the moving core The calibration is inscribed on the dashpot and is varied by screwing the pot into the cover Time is varied by changing the number of holes in the bottom of the piston uncovered by the dia phragm Instantaneous tripping is possible because the check valve action of the washer at the time of tripping varies inv...

Page 11: ...oltage reset spring retrieving the armature to its fully closed position Failure to reset the undervoltage armature completely will result in im proper operation as the holding coil is not capable of picking up the armature The turn buckle should clear the undervoltage armature during the tripping movement The turn buckle should be set to secure Ys clearance be tween the end of the slot in the mec...

Page 12: ...he control switch is reclosed while the breaker is in the latched position the moving core will move to the closed position 13 The cut off switch supplied on the later models is mounted on the right side of the mechanism frame just back of the auxiliary switch Figure 13 shows the position of the switch when the mecha nism is latched closed The switch used in this case is also a normally closed swi...

Page 13: ...ing lever and makes contact when the tripping lever is in the normal position and breaks contact when the tripping lever is raised Operation Counter The operation counter mounts on the upper auxiliary switch bracket After mounting in place and connecting to the auxiliary switch extension of the breaker lever the operation counter arm should be loosened and set so that only one number is recorded f...

Page 14: ... is best accomplished in the following manner 1 Wash with normal heptane obtainable from the major oil companies such as Esso Standard Use clean paper towels wet in the heptane Use a fresh towel on each part Caution Heptane is inflammable and no open flames or sparks should be allowed near the work 2 After the heptane has evaporated which re quires only a minute or two wash with de ionized water s...

Reviews: