MAINTENANCE
TESTING THE GROUND
FAULT SENSOR
1. Start the generator and allow it to warm up.
2. Press the test button on the ground fault sensor
(see Figure 62).
1
2
3
4
Figure 62 – Ground Fault Sensor Test
1 -
Test Button
2 -
Reset Button
3 -
Fault Light
4 -
Power Light
3.
The light next to “fault” will light and the main
breaker will trip.
4.
If the main breaker does not trip, the ground
fault sensor is not working correctly and must be
repaired before the generator can be operated.
5.
Press the reset button and reset the main breaker.
The light next to “fault” will go out and the light next
to “power” should light. Power will be restored to all
outlets.
CLEANING THE GENERATOR
It is important to inspect and clean the generator before
every use.
Clean All Engine Air Inlet and Outlet Ports –
Make
sure all engine air inlet and outlet ports are clean of any
dirt and debris to ensure the engine does not run hot
(see Figure 63
and
Figure 64)
.
Figure 63 – Engine Air Inlet and Outlet Ports – 10KPRO
Figure 64 – Engine Air Inlet and Outlet Ports – 8KPRO
Summary of Contents for 10KPRO
Page 1: ......
Page 4: ......
Page 10: ...10 SAFETY SAFETY LABELS AND DECALS 10KPRO 1 3 2 1 6 4 3 5 6 4 2 5 Figure 1 ...
Page 11: ...11 SAFETY 1 3 4 5 2 Class F 2 3 1 4 5 Figure 2 ...
Page 12: ...12 SAFETY SAFETY LABELS AND DECALS 8KPRO 1 3 2 1 5 4 3 5 4 2 Figure 3 ...
Page 13: ...13 SAFETY 2 6 3 1 5 4 1 3 4 5 6 2 Figure 4 ...
Page 52: ......
Page 53: ...MANUAL DEL PROPIETARIO ...
Page 56: ......
Page 62: ...10 SEGURIDAD ETIQUETAS Y CALCOMANÍAS DE SEGURIDAD 10KPRO 1 3 2 1 6 4 3 5 6 4 2 5 Figura 1 ...
Page 63: ...11 SEGURIDAD 1 3 4 5 2 Class F 2 3 1 4 5 Figura 2 ...
Page 64: ...12 SEGURIDAD ETIQUETAS Y CALCOMANÍAS DE SEGURIDAD 8KPRO 1 3 2 1 5 4 3 5 4 2 Figura 3 ...
Page 65: ...13 SEGURIDAD 2 6 3 1 5 4 1 3 4 5 6 2 Figura 4 ...
Page 104: ......
Page 105: ......
Page 106: ......