background image

WESTFIRE · WF

33

 · WF

34

 

WESTFIRE · WF

33

 · WF

34

7

stOVe Per FOr Mance & testing

Westfire UNIQ 33 & 34 have been approved in accordance with EN 13240.

Pr eparatory wor k and safety checks
Important warning

This stove must not be installed into a chimney that serves any other heating appliance. There must not be an
extractor fan fitted in the same room as the stove as this can cause the stove to emit fumes into the room.

Chimney
chimney connection
Flue diameter 150mm (175cm2)

iMPOr tant : When installing the uniQ 33 & 34 wood stoves remove steel retaining bar across flue exit.
remove bolts and take out bar replace and bolt cast onto collar.

In order for the stove to perform satisfactorily the chimney height must be sufficient to ensure an adequate
draught so as to clear the products of combustion and prevent smoke problems into the room.

Minimum draft: UNIQ 33, 34 stove has been tested with a draft of 12 Pa. Maximum draft 25 Pa.
Flue gas flow 6.0 g/sec.

Flue gas temperature 267°C. approximately 12 Pa.

NOTE: A chimney height of not less than 4.5 metres measured vertically from the outlet of the stove to the top of
the chimney should be satisfactory. Alternatively the calculation procedure given in BS 5854:1980 may be used as
the basis for deciding whether a particular chimney design will provide sufficient draught.

The outlet from the chimney should be above the roof of the building in accordance with the provisions of Build-
ing Regulations Approved Document J.

If installation is into an existing chimney then it must be sound and have no cracks or other faults which might
allow fumes into the house. Older properties, especially, may have chimney faults or the cross section may be
too large i.e. more than 160 mm x 160 mm. Remedial action should be taken, if required, seeking expert advice,
if necessary. If it is found necessary to line the chimney then a flue liner suitable for solid fuel must be used in
accordance with Building Regulations Approved Document J.
Any existing chimney must be clear of obstruction and have been swept clean immediately before installation of
the stove. If the stove is fitted in place of an open fire then the chimney should be swept one month after instal-
lation to clear any soot falls which may have occurred due to the difference in combustion between the stove and
the open fire.

If there is no existing chimney then either a prefabricated block chimney in accordance with Building Regulations
Approved Document J or a twin walled insulated stainless steel flue to BS 4543 can be used. These chimneys must
be fitted in accordance with the manufacturer’s instructions and Building Regulations.

A single wall metal fluepipe is suitable for connecting the stove to the chimney but is not suitable for using for
the complete chimney. The chimney and connecting fluepipe must have a minimum diameter of 150 mm and its
dimension should be not less than the size of the outlet socket of the stove.

uk

stove model 

Weight 

nominal heat output

Wood 

smokeless fuels

UNIQ 33 

118 kg 

6.1 KW 

N/A

UNIQ 34 

124 kg 

6.1 KW 

N/A

uk

Any bend in the chimney or connecting fluepipe should not exceed 45°. 90° bends should not be used.

If it is found that there is excessive draught in the chimney then either an adjustable flue damper or alternatively
a draught stabiliser should be fitted. The adjustable flue damper should not close off the flue entirely but should
in its closed position leave a minimum continuous opening free area of at least 20 % of the total cross sectional
area of the flue or fluepipe.

Adequate provision e.g. easily accessible soot door or doors must be provided for sweeping the chimney and
connecting flue pipe.

distance to combustible materials
Combustible materials should not be located where the heat dissipating through the walls of fireplaces or flues
could ignite it. Therefore when installing the stove in the presence of combustible materials due account must be
taken of the guidance on the separation of combustible material given in Building Regulations Approved Docu-
ment J and also in these stove instructions.

Hearth
The hearth should be able to accommodate the weight of the stove and its chimney if the chimney is not inde-
pendently supported.

The Westfire UNIQ 33, 34 wood stove has been tested and is suitable to be installed on a 12mm non combustible
plate such as Westfire 12mm glass plates or 20mm slate plates. Installation of all hearths should comply in size
and construction so that it is in accordance with the provisions of the current Building Regulations Approved Docu-
ment J.

The clearance distances to combustible material beneath, surrounding or upon the hearth and walls adjacent to
the hearth should comply with the guidance on the separation of combustible material given in Building Regula-
tions Approved Document J and also in these stove instructions.

If the stove is to be installed on a wooden floor, it must be covered with a non-combustible material at least
12mm thick, in accordance with Building Regulations Approved Document J, to a distance of 30 cm in front of the
stove and 15 cm to each side measuring from the door of the combustion chamber.

combustion air supply
In order for the stove to perform efficiently and safely there should be an adequate air supply into the room in
which the stove is installed to provide combustion air. This is particularly necessary if the room is double-glazed
or a flue draught stabiliser is operating in the same room as the appliance. The provision of air supply to the
stove must be in accordance with current Building Regulations Approved Document J. An opening window is not
appropriate for this purpose. Air inlets must be positioned in such a way that they cannot be blocked. An air inlet
may be a vent (the vent must be open and the capacity of the vent sufficient when the stove is lit) or a fresh air
system linked to the stove.

The UNIQ 33 & 34 are available with a closed air supply collar (additional item) this enables the stove to take
combustion air directly from outside with a 100 mm pipe from the stove.

There are no European rules regarding the minimum distance to non-flammable walls, Westfire recommend leav-
ing a gap of at least 10 cm behind and to sides of stove.

uniQ 33,34

Distance to combustible materials rear 

200 mm

Distance to combustible materials side 

350 mm

Distances to flammable materials/furnitures 

1000 mm

Summary of Contents for WF33

Page 1: ...st WF33 WF34 dk INSTALLATIONS OG BRUGSVEJLEDNING 3 uk INSTALLATION MANUAL AND OPERATING INSTRUCTIONS 6 d INSTALLATIONS UND GEBRAUCHSANWEISUNG 15 Fr NOTICE D INSTALLATION ET D UTILISATION 18 nL INSTALLATIEHANDLEIDING EN GEBRUIKSAANWIJZING 21 ...

Page 2: ...nselem Bag cm siden cm Møbleringsafstand Foran cm WF 33 WF 34 20 cm 35 cm 100 cm dk WF 33 og WF 34 er godkendt efter europæ iske standard EN 13240 Den nominelle varmeydelse er 6 1 kW WF 33 har en afprøvningsvæ gt på 118 kg WF 34 har en afprøvningsvæ gt på 124 kg Minimumsrøgtræ kket Ovnen er afprøvet med et røgtræ k på 12 Pa Max røgtræ k 25 Pa Røggasmasseflowet er 6 0 g sek Røggastemperaturen er må...

Page 3: ...kke skader på udskiftelige dele transportomkostninger i forbindelse med garantireparationer eller montering demontering ved garantireparationer Der advares mod enhver uautoriseret æ ndring af anordningen Ved reparation brug alene reservedele anbefalet af Westfire ApS uk uk Installation ManuaL and Oper ating instructions WestFire WF UNIQ 33 WF UNIQ 34 this manual refers to the stove type listed abo...

Page 4: ...necting fluepipe should not exceed 45 90 bends should not be used If it is found that there is excessive draught in the chimney then either an adjustable flue damper or alternatively a draught stabiliser should be fitted The adjustable flue damper should not close off the flue entirely but should in its closed position leave a minimum continuous opening free area of at least 20 of the total cross ...

Page 5: ...roduces a good deal of smoke and odour it is therefore important that the first time you light your stove the room should be well ventilated During the process it is important to open and close the stove door periodically every 30mins during the first couple of firings therefore preventing the door seal cord around the door from sticking and coming away from the door Once the Heat resistant paint ...

Page 6: ...ance UNIQ 33 34 wood stove needs to have the ash removed from the stove at regular intervals Make sure the stove is completely cold before cleaning out ash embers can remain hot for over 24 hours To clean the outside of the stove use a dry cloth annual service The inside of the stove should be serviced cleaned once a year To clean the inside remove all ash soot and tar residue from the combustion ...

Page 7: ...o burn solid fuel in those areas other than authorised fuels have been exempted by an Order made and signed by the Secretary of State or Minister in the devolved administrations Further information on the requirements of the Clean Air Act can be found here http smokecontrol defra gov uk Your local authority is responsible for implementing the Clean Air Act 1993 including designation and supervisio...

Page 8: ...utdown period If the stove is fitted in place of an open fire then the chimney should be swept one month after installation to clear any soot falls which may have occurred due to the difference in combustion between the stove and the open fire In situations where it is not possible to sweep through the stove the installer will have provided alternative means such as a soot door After sweeping the ...

Page 9: ...uss dort wo der Kaminofen stehen soll ausreichend tragfähig sein Der Abstand zu brennbaren Materialien gem EN 13240 geht aus dem Schild auf der Ofenrückseite hervor Bei nicht brennbaren Wänden gibt es keine Vorschriften jedoch empfehlen wir wegen der bequemeren Reinigung mindestens 10 cm hinter dem Ofen frei zu lassen Weil Verbrennung Luft erfordert ist für eine ausreichende nicht blockierbare Fri...

Page 10: ...le sowie Kosten für Transport oder Auf Abbauarbeiten im Zuge von Garantie Reparaturen Die Garantie erlischt bei unbefugten technischen Änderungen am Ofen Bei Reparaturen sind ausschließlich von der Fa Westfire ApS empfohlene Ersatzteile zu verwenden d d Das Rauchrohr ist mit einer Regulierklappe erhältlich die es ermöglicht den Schornsteinzug an Tagen mit starkem Wind zu regulieren Sie darf sich n...

Page 11: ...a fumée passe bien à travers la cheminée le tirage est satisfaisant air secondaire WF 33 WF 34 Ouverture à 50 Fr Fr Fr nOtice d instaLLatiOn et d utiLisatiOn WestFir e WF33 WestFir e WF34 Nous vous félicitons pour l achat de votre nouveau poêle fabriqué par Westfire ApS Pour en profiter pleinement et vous éviter toute difficulté nous vous invitons à lire attentivement cette notice Nous attirons vo...

Page 12: ...raité Utilisez toujours du bois sec Le niveau de sécheresse du bois joue un rôle capital car lorsque le bois est humide la combustion coûte plus cher et il y a formation de bistre Le bois fraî chement coupé contient entre 60 et 70 d eau ce qui le rend absolument impropre comme combustible Il doit d abord être entreposé et mis à sécher au vent sous un auvent pendant deux ans avant de pouvoir servir...

Page 13: ...gesloten Gasgestookte warmtebronnen moeten altijd hun eigen schoorsteen hebben waarop geen andere warmtebronnen mogen zijn aangesloten BedieningsHandLeiding Als u de houtkachel voor het eerst aansteekt zal de hittebestendige verf harden waardoor er nogal wat stank en rook ontstaat Zorg daarom voor een goede ventilatie De eerste paar keer dat u de haard aansteekt moet u ook de deur een klein eindje...

Page 14: ...24 Tø MRERVEJ 3 DK 6800 VARDE TELEFON 45 7522 5352 FAx 45 7522 1352 WWW WESTFIRE DK E MAIL INFO WESTFIRE DK WESTFIRE 2012 Der tages forbehold for trykfejl 18540 Mediegruppen Reklamebureau ...

Reviews: