InstRUCtIOns FOR FIttERs
18. aDjUstMEnt anD saFEtY DEvICEs
This boiler has been designed in full compliance with European reference standards and, in particular, it is fitted with the following:
• safety thermostat
Thanks to a sensor placed on the heating delivery line, the thermostat interrupts the flow of gas to the burner if the water in the
primary circuit overheats. In these conditions, the boiler is blocked and only after the fault has been eliminated will it be possible to
light it again by pressing the reset button on the boiler control panel.
It is forbidden to disable this safety device
• Fumes thermostat
This device, positioned on the fumes evacuation duct inside the boiler, interrupts the flow of gas to the burner in case of temperatures
higher than 90 °C. Press the reset button on the thermostat, eliminate the fault and then press the reset button on the boiler control
panel.
It is forbidden to disable this safety device
• flame ionisation detector
The flame sensing electrode guarantees safety of operation in case of gas failure or incomplete ignition of the main burner.
In these conditions, the boiler blocks.
Press the reset button on the boiler control panel to re-establish normal operating conditions.
• Hydraulic differential pressure switch
This device, mounted on the hydraulic unit, only allows the main burner to light if the pump is able to deliver the necessary head. It
protects the water-fumes exchanger if there is no water or if the pump blocks.
• pump post-circulation
The electronically-controlled pump post-circulation function lasts 3 minutes and is enabled, in the heating mode, if the ambient
thermostat causes the main burner to go out.
• Frost protection device
The electronic boiler management system includes a “frost protection” function in the heating and DHW modes which, if delivery
temperature falls below 5°C, operates the burner until a delivery temperature of 30°C is reached.
This function is enabled when the boiler is switched on, the gas supply is open and the system is correctly pressurised.
• anti-block pump function
If no heat demand is received in the heating and/or DHW modes for 24 consecutive hours, the pump will automatically start and
operate for 10 seconds.
• three-way valve anti-blockage function
If no heat demand is received for a period of 24 hours, the three-way valve performs a complete switching cycle.
This function is operative when the boiler is powered.
• Hydraulic safety valve (heating circuit)
This device is set to 3 bar and is used for the heating circuit.
Connect the safety valve to a drain trap. Do not use it to drain the heating circuit.
Summary of Contents for NOVADENS BOYLER 240
Page 64: ...64 926 091 1 RU 3 1 2 3 1 0510_2801 1 2 3 5 6 7 8 9 10 b a...
Page 68: ...68 926 091 1 RU 3 8 1 4 020503_0500 4 0510_2001 4 1 1 4 1...
Page 70: ...70 926 091 1 RU 1 1 5 5 4 5 0806_0501 0210_1119 5 5 30 6 7 5 8...
Page 71: ...71 926 091 1 RU a 1 20 F 1 F 10 2 2 1 2 2 SENTINEL 400 100 22 9 10...
Page 75: ...75 926 091 1 RU 14 3 60 100 L 10 L 10 L 9 L 8 0210_1112 100 80 0510_2802 90 360 45...
Page 85: ...85 926 091 1 RU 18 90 3 5 30 24 10 24 3...
Page 86: ...86 926 091 1 RU 19 16 010905_0200 20 26 1993 412 2 2 17 020429_0300...
Page 87: ...87 926 091 1 RU 21 1 2 3 3 6 2 020429_0200 18 A 4 19 0210_1801 22 23...
Page 88: ...88 926 091 1 RU 24 4 1 1 1 4 4 19 0302_2701 25...
Page 90: ...90 926 091 1 RU 27 N R G V 0305_1204 230...
Page 124: ...124 926 091 1 EL 3 1 0510_2801 1 2 3 5 6 7 8 9 10 b a reset on off Standby...
Page 128: ...128 926 091 1 EL 3 8 1 a 4 reset 020503_0500 4 0510_2001 4 1 1 b 4 1 reset...
Page 130: ...130 926 091 1 EL 1 1 5 bar 5 4 5 0806_0501 0210_1119 5 5 C 30 C 6 7 GPL 5 8...
Page 145: ...145 926 091 1 EL instructions for fitters 18 reset 90 C reset reset 3 5 C 30 C 24 10 24 3 bar...
Page 146: ...146 926 091 1 EL instructions for fitters 19 16 010905_0200 20 2 CO2 CO 17 020429_0300...
Page 148: ...148 926 091 1 EL instructions for fitters 24 4 bar 1 1 1 4 bar 4 bar 19 0302_2701 25...
Page 150: ...150 926 091 1 EL instructions for fitters 27 C M N R G V B 0305_1204 230V NTC CRO NTC...