19
96.091.1 - GB
InstRUCtIOns FOR FIttERs
line n°
70
7
74
75
77
78
79
80
90
91
Factory setting
15
85
Light
On HC1
Active
0
0
—.-
10
24 h/day
Range
2.5…40
25…85
Light, Heavy
on HC1
on HC2
on HC1+HC2
off
Inactive - active
0…360 min
0…360 min
2.5…40
—.-
= inactive
10 or 35…58
24 h/day PROG
HC-1h PROG HC
PROG ACS
parameter
HC1 gradient
Selection of climate curve “kt” of the heating circuit
HC1 Max Delivery
Maximum heating delivery temperature
Type of building
Environment offset
Enable / disable effect of ambient temperature. If disabled, the external
probe must be fitted.
Automatic adaptation of “kt” climate curve according to ambient
temperature.
Max start optimisation
Maximum boiler start anticipation, with respect to the hourly
programme, for optimising room temperature.
Max stop optimisation
Maximum boiler stop anticipation, with respect to the hourly
programme, for optimising room temperature.
HC2 gradient
Reduced ACS setpoint
Minimum DHW temperature
ACS programme
Choice of the type of hourly DHW programme.
24 h/days
= always active
PROG HC-1h
= as per heating programme HC1 less 1 hour
PROG HC
= as per heating programme
PROG ACS
= specific DHW programme (see also
programme lines 30-36)
- fault signals
In case of faults flashes on the QAA73 display. Press the information button ( ) to display the error code and the description of the
fault (see the table in paragraph 3.9).
Summary of Contents for NOVADENS BOYLER 240
Page 64: ...64 926 091 1 RU 3 1 2 3 1 0510_2801 1 2 3 5 6 7 8 9 10 b a...
Page 68: ...68 926 091 1 RU 3 8 1 4 020503_0500 4 0510_2001 4 1 1 4 1...
Page 70: ...70 926 091 1 RU 1 1 5 5 4 5 0806_0501 0210_1119 5 5 30 6 7 5 8...
Page 71: ...71 926 091 1 RU a 1 20 F 1 F 10 2 2 1 2 2 SENTINEL 400 100 22 9 10...
Page 75: ...75 926 091 1 RU 14 3 60 100 L 10 L 10 L 9 L 8 0210_1112 100 80 0510_2802 90 360 45...
Page 85: ...85 926 091 1 RU 18 90 3 5 30 24 10 24 3...
Page 86: ...86 926 091 1 RU 19 16 010905_0200 20 26 1993 412 2 2 17 020429_0300...
Page 87: ...87 926 091 1 RU 21 1 2 3 3 6 2 020429_0200 18 A 4 19 0210_1801 22 23...
Page 88: ...88 926 091 1 RU 24 4 1 1 1 4 4 19 0302_2701 25...
Page 90: ...90 926 091 1 RU 27 N R G V 0305_1204 230...
Page 124: ...124 926 091 1 EL 3 1 0510_2801 1 2 3 5 6 7 8 9 10 b a reset on off Standby...
Page 128: ...128 926 091 1 EL 3 8 1 a 4 reset 020503_0500 4 0510_2001 4 1 1 b 4 1 reset...
Page 130: ...130 926 091 1 EL 1 1 5 bar 5 4 5 0806_0501 0210_1119 5 5 C 30 C 6 7 GPL 5 8...
Page 145: ...145 926 091 1 EL instructions for fitters 18 reset 90 C reset reset 3 5 C 30 C 24 10 24 3 bar...
Page 146: ...146 926 091 1 EL instructions for fitters 19 16 010905_0200 20 2 CO2 CO 17 020429_0300...
Page 148: ...148 926 091 1 EL instructions for fitters 24 4 bar 1 1 1 4 bar 4 bar 19 0302_2701 25...
Page 150: ...150 926 091 1 EL instructions for fitters 27 C M N R G V B 0305_1204 230V NTC CRO NTC...