background image

Section 311-580-20B

030-101527 Rev. B

13

0407IBRB

CAUTION

Risk of electric shock. Voltages up to 140 VDC (with reference to
ground) may be present on telecommunications circuits.

- PRECAUTIONARY STATEMENT -

- Never install telephone wiring during a lightning storm.

- Never install telephone jacks in wet locations unless the jack is

specifically designed for wet locations.

- Never touch uninsulated telephone wires or terminals unless

the phone line has been disconnected at the network interface.

- Use caution when installing or modifying telephone lines.

- This equipment is intended to be used behind devices that

provide primary lightning protection.

- This installation should conform to Local Codes and NEC

requirements.

- This equipment is to be installed in a restricted access location.

- CAUTION -

Never apply power until all installer connections are made.

8.2

Mounting the Module

The 3115-80 is a 200 MECHANICS

-type plug-in module that

mounts in a 200- or 400-mechanics-type mounting assembly (or
equivalent mounting which matches the pin-out plan of the
module). Before installing the module, set any options in the de-
sired position(s). Align the module with the mounting or
assembly card guides above and below the unit and insert as far
as it will go into the slot connector.

Function

Designation

Pin Number

FAC IN

T

7

R

13

CPE OUT

CT1

5

CR1

15

CPE IN

CT

55

CR

49

FAC OUT

T1

41

R1

47

LOCAL POWER

-Local Power

35

Ground

17

Frame Ground

FRM GND

27

Table 6.    3115-80 Pin Designations

8.3

Making Installer Connections

No installer connections are required other than inserting the
module into the card-edge connector in the shelf or assembly.
The unit makes electrical connections to external equipment
when installed and properly seated in the 56-pin card-edge con-
nector in the mounting assembly. The pin-outs used by the NIU
are listed in Table 6.

- CAUTION -

Use care when installing and removing modules - 

do not force

into place

. If a module resists insertion, remove it and check

for obstructions in/near the connectors and mounting slots,
then carefully re-align and gently re-insert the module.

NIU’s

DB-9

Connector

Baud rate:  9600
Number of data bits: 8
# of start/stop bits:  1
Parity:  none
Local Echo: No/Off

Warning Bell: On

Mode:  VT100

Auto Line Wrap: No/Off

Standard

RS-232

Cable

(used with

PC with

VT100

emulator).

Terminal

Settings:

Figure 12. Preparing for Provisioning Via DB-9 Port

200 MECHANICS or

400-type mounting

assembly

9.

SET-UP AND OPERATION

9.1

Craft Terminal Setup and Operation

9.1.1

The front-panel craft interface port allows the craft to

configure the unit for a particular application, view the stored T1
performance statistics, as well as graphically view circuit status
and perform various test routines. Each menu provides an asso-
ciated HELP screen that explains the function and use of the
menu. HELP screens are accessed by pressing (?).

9.1.2

The craft interface port is a DB-9 connector with an

electrical RS-232 female interface in a DCE configuration. The
craft device can be a terminal operating in the VT-100 protocol
or a PC running a VT-100 terminal emulator program. If a
VT-100 terminal is used a null-modem" cable may be required
between the terminal and the NIU. If a PC with VT-100 emula-
tor program is used, a standard RS-232 cable can be used. The
RS-232 port should be set up for 9600 baud, no parity, and one
stop bit (NP,1S). The electrical connections to the craft port are
shown in Figure 10.

9.2

Menus and Screens

9.2.1

MAIN Menu Screen

Once the terminal or PC is connected to the craft interface port,
the MAIN menu should appear. The MAIN menu provides the
NIU model number, CLEI code, Technical Service contact tele-
phone number, as well as navigation buttons to other screens.
The Model Number and CLEI Code are set at the factory and
cannot be changed. The MAIN menu is illustrated in Figure 14.
To return to the MAIN menu screen from any other screen enter
<Esc>.

9.2.2

PROVISIONING Menu Screen

The PROVISIONING screen (Figure 15) is used to configure
the unit’s options. To reach this screen from the MAIN menu,
type <O>. The NIU is set from the factory to a standard config-
uration. All options in the menu can be set and queried
remotely. For each option, the display shows the CURRENT"
configuration as well as a NEW" field that shows what the op-

Summary of Contents for PROACT 3115-80

Page 1: ...3 and updates Paragraphs 9 2 4 4 through 9 2 4 7 Paragraph 9 2 9 Table 7 Table 11 Table 12 Figure 13 Figure 15 Figure 16 Figure 17 Figure 25 and Figure 27 The Issue B equipment provides the following...

Page 2: ...es in the Data Link by use of a Test Head without affecting customer payload Remote non intrusive real time reporting of PM pa rameters via 1 second NPRM or SPRM reports in the Data Link per ANSI T1 4...

Page 3: ...m 24Vdc supplies at certain wireless and PCS Personal Communication Service sites In the local power mode the NIU completes the T1 span simplex power loop and drops negligible span voltage 2 2 2 Span...

Page 4: ...no net regeneration from input to output In this case the signal is connected directly to the CPE to FAC LBO circuit 3 2 2 CPE to FAC LBO 3 2 2 1 LBO Line Build Out is an artificial line used to meet...

Page 5: ...not effect the unit s transmission path When the Moni tored Line Coding is set for AMI occurrences of 16 consecutive 0 s will be disregarded and occurrences of B8ZS octets will be re flected in the B8...

Page 6: ...NIU for the proper duration These control code sequences are listed in Table 1 Function Code Type DS1 T1 Activate 11000 Unframed SF or ESF Loop Up 0001 0010 1111 1111 ESF DATA LINK1 DS1 T1 11100 Unfr...

Page 7: ...eleased via the craft interface port or 4 when the MAN LB switch is pressed for 5 seconds 5 SECTIONALIZATION ALARM FEATURES The NIU is equipped with features that allow a network moni toring location...

Page 8: ...m Indication Signal AIS to ward the customer equipment The customer equipment in turn will send a Remote AIarm Indication RAI signal back to wards the network 6 PERFORMANCE MONITORING REPORTING The un...

Page 9: ...it basis and places the NIU in loopback If the circuit is SF the test con troller must then reconfigure for ESF framing for the duration of the session to allow commands and responses to be exchanged...

Page 10: ...ast four sec onds of operation This NPRM is inserted into the Data Link by the NIU after the 1 second PRM from the customer CSU that is passed through the NIU Note that the CSU may not generate PRMs o...

Page 11: ...ustomer back to the network This bit will be a logic 1 if a condition is detected in the signal which would nor mally result in conversion of any bit in a PRM from 0 to 1 Each U2 bit carries informati...

Page 12: ...tates SPAN LOC Top Edge of PCB Edge Connector 56 pin of PCB Figure 11 NIU Powering Option Location Middle of Side panel s Printed Circuit Board Gray shaded rectangle is the pin jumper P201 When first...

Page 13: ...en carefully re align and gently re insert the module NIU s DB 9 Connector Baud rate 9600 Number of data bits 8 of start stop bits 1 Parity none Local Echo No Off Warning Bell On Mode VT100 Auto Line...

Page 14: ...ailable options under the NEW field 9 2 2 1 Saving The Changed Options After configuring the options press S to save the new set tings Note If you enter Esc without saving the system will give a messa...

Page 15: ...Configures the unit to send SPRM messages SPRM NPRM Configures the unit to send both SPRM and NPRM messages CPE to FAC REGEN Regen Off No regeneration in the CPE to FAC Z A XMT path Regen On Regenerat...

Page 16: ...ports to the T1 facility and customer interface 9 2 4 2 For each port the screen shows 1 Level LVL of the signal in dB Possible field values are 0 0dB level detected 1 1dB level detected 2 2dB level...

Page 17: ...pa rameters and options in the loopback path Figure 20 shows the NIU in a single loopback mode when FAC to CPE Regenera tion is Enabled 9 2 4 7 Using the Ctrl D keys simultaneously will cause the NIU...

Page 18: ...B90 311580 CIRCUIT STATUS CLEI T1S1ABTAAA LVL 0 5dBdsx LVL 0 0dBdsx FRMG SF 3115 80 FRMG UNF UNK SIG OK SIG AIS TO FAC AIS TO CPE REGEN LVL 0 5dBdsx Facility Loopback LVL 8 0dBdsx FRMG SF FRMG SIG OK...

Page 19: ...The Event Alarm Log can be viewed locally via the craft interface port An example of a typical Event Alarm Log screen is shown in Figure 22 The Event Alarm Log can also be retrieved re motely via TL1...

Page 20: ...then select Start 3 Select a report number 1 2 3 or 4 to capture data from the SEND DATA TO LOG FILE menu 4 After download is complete select Transfer Capture Text and Stop from HyperTerminal 9 2 10...

Page 21: ...ill allow the unit to operate directly from T1 metallic spans or from a locally provided 22 to 56Vdc source The NIU is fused on its local power input lead pin 35 to prevent the failure of an individua...

Page 22: ...ll Once an RMA number is obtained return the defective unit freight prepaid along with a brief problem description to Westell Inc ATTN R G M Department 750 N Commons Drive Aurora IL 60504 7940 Replace...

Page 23: ...PE to FAC 15 dB WSTTRMTLBO 15 1100 0100 1011 0101 C4B5 22 5 dB WSTTRMTLBO 22 5 1100 0100 1011 0110 C4B6 AB15 dB WSTTRMTLBO AB15 1100 0100 1011 0111 C4B7 AB22 5 dB WSTTRMTLBO AB22 5 1100 0100 1011 1000...

Page 24: ...TPM None 1100 0101 1101 0000 900 None NPRM C5D0 1900 NPRM Enabled SPRM C5D0 3000 SPRM Enabled SPRM NPRM 2500 SPRM NPRM Enabled Loopback Time out WSTLBTO DIS 900 Disabled p 20 920 20 Minutes 60 1101 01...

Page 25: ...80 6 dB 7 dB 8dB 120 130 140 12 dB 13 dB 14 dB 180 190 200 18 dB 19 dB 20 dB Facility Level Query 1100 0101 0110 1111 Unframed SF or ESF C56F 20 40 30 50 2 dB 4 dB 3 dB 5 dB 80 90 100 110 8dB 9dB 10 d...

Page 26: ...tnm optstg cr lf List of Options This is a comprehensive list of command line options Simply use the codes identified in the columns below when configuring command lines OPTION OPTNM OPTSTG Monitored...

Reviews: