ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
Page 114
Modbus Parameters
59407, Issue 3 – May 2011
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Enable Edit While
Running
8262
0x2046
R/W
Value
Editing Current Running Profile
0
Editing current running profile forbidden
1
Editing current running profile allowed
Profile Control In
Operation Mode
8260
0x2044
R/W
Value
Profile Control From Operation Mode
0
Operation Mode profile control disabled
1
Operation Mode profile control enabled
Profile Cycles Run
8247
0x2037
RO
The Number of times the currently running profile has
cycled
Event 1 Status
8249
0x2039
RO
Value
Status Of Event 1
0
Event 1 Inactive
1
Event 1 Active
Event 2 Status
8250
0x203A
RO
Value
Status Of Event 2
0
Event 2 Inactive
1
Event 2 Active
Event 3 Status
8251
0x203B
RO
Value
Status Of Event 3
0
Event 3 Inactive
1
Event 3 Active
Event 4 Status
8252
0x203C
RO
Value
Status Of Event 4
0
Event 4 Inactive
1
Event 4 Active
Event 5 Status
8253
0x203D
RO
Value
Status Of Event 5
0
Event 5 Inactive
1
Event 5 Active
Segment Type
Status
8258
0x2042
RO
Value
Segment Type Status
0
No segment
1
Setpoint ramping up
2
Step
3
Dwell
4
Held
5
Loop
6
Join
7
End
8
Setpoint ramping down
Currently Active
Profile Name
8259
0x2043
RO
The name of the currently selected profile
Secondary Profile
Status
8232
0x2028
RO
Value
0
Profile running
1
Input sensor break
2
Profile not valid
3
Controller in manual mode
4
Profile finished. Profiler is maintaining the
last profile setpoint
5
Profile finished with control outputs off
6
Profile control has ended. Unit is
Controller Mode.
Delay time
8233
0x2029
RO
The current start delay time remaining