ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
Page 108
Modbus Parameters
59407, Issue 3 – May 2011
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Recording Mode
7551
0x1D7F
R/W
Value
Recording Mode
0
Record until memory used
1
Continuous FIFO buffer
Start Stop
Recording
7552
0x1D80
R/W
Value
Operator Start/Stop Recording
0
Stop Recording
1
Start Recording
Data Recorder
Fitted
7553
0x1D81
RO
Value
Data Recorder Fitted
0
Not Fitted
1
Recorder Fitted
Memory Remaining
7554
0x1D82
RO
Memory unused remaining left, in bytes
Time Remaining
7555
0x1D83
RO
Time remaining until memory is used up, in seconds
Recorder Trigger
7563
0x1D8B
R/W
Value
Recorder Trigger
0
Operator start/stop
1
Recorder Menu start/stop
2
On Alarm (
see Alarm 1-5 trigger below
)
3
Digital input A
4
Digital input B
5
During running of profiles
Record Process
Variable
7572
0x1D94
R/W
Value
Record Process Variable
0
Do Not Record PV
1
Record PV Value
Record Maximum
PV Between
Samples
7573
0x1D95
R/W
Value
Record Max PV Since Last Sample
0
Do Not Record Maximum PV
1
Record Maximum PV Between Samples
Record Minimum PV
Between Samples
7574
0x1D96
R/W
Value
Record Min PV Since Last Sample
0
Do Not Record Minimum PV
1
Record Minimum PV Between Samples
Record Actual
Setpoint
7575
0x1D97
R/W
Value
Record Actual Setpoint Value
0
Do Not Record Setpoint
1
Record Actual Setpoint
Record Primary
Power
7576
0x1D98
R/W
Value
Record Primary Power Value
0
Do Not Record Primary Power
1
Record Primary Power
Record Secondary
Power
7577
0x1D99
R/W
Value
Record Secondary Power Value
0
Do Not Record Secondary Power
1
Record Secondary Power
Record Alarm 1
Status
7578
0x1D9A
R/W
Value
Record Change Of State For Alarm 1
0
Do Not Record Alarm 1
1
Record Alarm 1
Record Alarm 2
Status
7579
0x1D9B
R/W
Value
Record Change Of State For Alarm 2
0
Do Not Record Alarm 2
1
Record Alarm 2