Long-Range Laser Distance Sensors
Order No.
Technical Data
P1PY
101
111
102
103
113
104
107
108
Setting range
50 – 10,000 mm
—
Measuring range
—
50 – 10,000 mm
Switching hysteresis
< 15 mm
—
Current consumption (operat-
ing voltage = 24 V)
< 35 mA
< 40 mA
Switching frequency
50 Hz*
—
Response time
15 ms
—
Measuring rate
—
100/s*
Acceleration sensor
—
Yes
—
—
Yes
—
—
Connection diagram no.
243
241
242
Connection type
1x M12; 5-pin
Cable with
1×M12
5-pin plug
1×M12; 5-pin
Cable with
1×M12
5-pin plug
1×M12;
5-pin
1×M12;
5-pin
Cable length (L)
—
500 mm
—
500 mm
—
—
Output function
2× PNP NO
2× NPN NO
Analog
0 – 10 V
Analog
4 – 20 mA
MTTFd (EN ISO 13849-1)
574,59 a 543,26 a
574,59 a
574,59 a 543,26 a
574,59 a
508,83 a
512,61 a
“3.4 Mode-Dependent Data” on page 10
3.2 Warm-up phase
The warm-up phase lasts 6 minutes. The switching on drift during that time can be seen in the following
diagram.
0
60
120
180
240
300
–7
–5
–6
–4
–3
–2
Time in sec.
Typ. deviation in mm
–1
Switching On Drift
360
0
NOTE!
Specifiations related to the measured value without load. For the analog versions this spec-
ification can deviate due to the load on the analog output.