14
EN
External Minimal Teach-In
(see also fig. 7 and 8)
Initialise minimal Teach-In: Set rotary selector switch to Teach, press the minus button twice, set rotary selector
switch to Run)
• Set rotary selector switch (07) to Run
• Apply 10 V to 30 V to the Teach-In input (in relation to minus pole, for at least 0.3 sec)
è
Red LED (02) blinks
• Disconnect voltage from the Teach-In input
è
Teach-In process ensues
è
Red LED (02) stops blinking
External Dynamic Teach-In
(see also fig. 9)
Initialise dynamic Teach-In: Set rotary selector switch to Teach, press and hold the plus button for 5 sec, release
the plus button, set rotary selector switch to Run)
• Set rotary selector switch (07) to Run
• Apply 10 V to 30 V to the Teach-In input (in relation to minus pole, for the duration of recording)
è
Red LED (02) blinks
• Disconnect voltage from the Teach-In input
è
Teach-In process ensues
è
Red LED (02) stops blinking
4.7. Selecting the Run function
4.7.1. Normal operating mode
• Set rotary selector switch (07) to Run
è
Red LED (02) blinks if contamination is detected
è
Yellow LED (01) indicates switching status
è
The plus button (24) and the minus button (25) are disabled