SELF-DIAGNOSTIC ALARM CODES

Alarm Display

Problem

Cause

Correc  ve Ac  on

Frost preven  on
sensor and Abnor-
mal
temperature sensor 
value

•  Indoor heat exchanger 

temperature too low

•  TH3 temperature sensor  

has a loose or broken 
connec  on

•   Do not use the air 

condi  oner if ambient 
temperature is lower than 
18°C (64°F)

•  Contact a quali

fi

 ed service 

agent

Refrigerant high
pressure switch

• Blocked air 

fi

 lter

•  Ambient temperature is 

too high

•  Leak/cut o

  supply 

water

• Clean air 

fi

 lter

•  Do not use the air 

condi  oner if ambient 
temperature is higher 
than 50°C (122°F)

•  Check water 

fl

 ow

Abnormal tempera-
ture sensor value

TH1(Outlet) temperature 
sensor has a loose or 
broken connec  on

Contact a quali

fi

 ed service 

agent

Abnormal tempera-
ture sensor value

TH2(Inlet) temperature 
sensor has a loose or
broken connec  on

Contact a quali

fi

 ed service 

agent

Compressor over-
loaded

•  Ambient temperature is 

too high

•  Unstable voltage
   supply
•  Defec  ve compressor
•  Over current relay 

defect or broken           
connec  on

•  Do not use the air 

condi  oner if ambient 
temperature is higher 
than 50°C (122°F)

•  Contact a quali

fi

 ed service 

agent

• Replace compressor

Condensate water 
level alarm

Condensate tank is full

•  Empty the water tank
•  A  er installa  on of the 

water tank, press the 
SPOT/COOL or ROOM/
COOL bu  on to resume 
opera  on

Drain pump alarm

Drain pump defec  ve or 
improper hose connec-

 on (including kink or 

blockage)

•  Check the hose connec-

 on and hose

• Replace drain pump

Table 1- Alarm Codes

Summary of Contents for AMERICOOL

Page 1: ...t can be installed by connec ng water line easily without installa on of duct Automa c water adjust valve control condenser water flow rate according to inlet water temperature It helps to supply prop...

Page 2: ...ing for large areas where cooling of an en re area is not prac cal or possible Please read this manual before installing the WPW 4000 as it provides important informa on that should be followed during...

Page 3: ...PW 4000 0 56 0 84 1 36 Model No Se ng temperature Room cool mode F C Se ng temperature Spot cool mode F C WPW 4000 64 86 18 30 32 86 0 30 Model No Applica on Area Room cool mode m Refrigerant Type oz...

Page 4: ...unit 13 DO NOT operate the unit in the presence of flammable substances or vapors such as alco hols pes cides gasoline etc 14 DO NOT use the plug to start and to stop the unit Always use the control p...

Page 5: ...24 If water supply volume is small the unit is not operated properly and main component can get damaged 25 Stop opera on immediately if abnormal noise or odor is no ced Contact a local service center...

Page 6: ...carton 2 Placetheairductassemblyonthetopfrontof unit 3 Usescrews enclosedinsideofboxwithcoolair ductassembly ontheunitasshowninFigure5 Figure 2 Front and Right Side View Figure 3 Back and Le Side View...

Page 7: ...Takeoutthehose2pcsfromtheaccessorybox INLETHOSEincludea3 4 hosebarbforconnec ngplumbing or boosterpump OUTLETHOSEisjusthose 2 Connecthoseandtheendofcouplerand eupbyhoseclampas showninFigure6 No ce Don...

Page 8: ...ny other foreign material The unit is equipped with an approved NEMA plug configura on WPW 4000 5 15P The ap propriate outlet must be used for each plug type WARNINGS REGARDING PROPER LOCATION FOR INS...

Page 9: ...a on If Alarm oc curs compressor stops System opera on stops when ALARM light is ac vated blinks longer than 3 minutes 7 CURRENT TEMP Displays current room temperature in display in Fahrenheit In Room...

Page 10: ...r and war ranty period in the table below Also a ach your purchase receipt as proof of purchase to this instruc on manual for future reference To ensure your product is covered by warranty the complet...

Page 11: ...stop opera ng The evaporator fan will con nue to run for 3 minutes If the fault is rec fied within 3 minutes the unit will resume opera on If the fault persists for more than 3 minutes the evaporator...

Page 12: ...tlet temperature sensor has a loose or broken connec on Contact a qualified service agent Abnormal tempera ture sensor value TH2 Inlet temperature sensor has a loose or broken connec on Contact a qual...

Page 13: ...Owner s Manual WPW 4000 Wiring Diagram Figure 12 Circuit Wiring Diagram POWER 1P AC 115V 1P AC 208 230V 115V 220V POWER DRAIN PUMP option FD FD FD TR...

Page 14: ...ed if the filter is dirty and not regularly cleaned 1 Clean the filter 2 Compressor will not work if the unit is turned o and on quickly 2 Wait 2 minutes a er unit is turned o before turning the unit...

Page 15: ...562 231 7175 Please have the following informa on available BEFORE calling the Technical Support Department a Your name and address b The serial number of the unit c Where and when the unit was purcha...

Page 16: ...vi modifica ons or altera ons to the Products vii use with parts or devices not supplied or approved by AmeriCool viii improper installa on or service ix shipping damage to any units or spare parts d...

Reviews: