- 10 -
9
DCAU: DC auto restart function
Note: If select “Y”, check whether the
configured time in “DC auto restart time” is
correct or not, if not, change it.
N
Y / N
10
ACAU: AC self-starting function
Y
Y / N
11
INP: Input power matching of the generator
120%
10% ~ 120%
(based on rated
power)
12
INLS: Inverter shutdown load rate
3%
3%
~
50%
(based on rated
power)
13
T: DC auto restart time
1H
0.5H ~ 8.0H
14
SAVE: Save and Exit
Y / N
4.4 Troubleshooting
This section lists the status and alarm messages that the UPS might display.
A suggested corrective action is listed with each display message to help
you troubleshoot problems.
No.
Problem Description
Display Message
Corrective Action
1
AC output short circuit
Check if the load is short circuited.
2
AC output voltage is too high
Contact the dealer or supplier from
whom it was purchased.
3
AC output voltage is too low
Contact the dealer or supplier from
whom it was purchased.