Installation Instructions 

Section 2

Refrigeration System Installation 

Remote Condensing Unit

QuietQube®  

Ice Machine

Remote Condensing 

Unit

Line Set*

RNF1100C 

RFF1220C 

RFF2200C

RCUF1000 

RCUF1200 

RCUF2200

RC-21  

RC-31  

RC-51

*Line Set

Suction Line

Liquid Line

RC 21/31/51

5/8 inch (15.9 mm)

3/8 inch (9.5 mm)

RACK UNIT CONNECTION SIZE

Model

Suction Line

Liquid Line

RFK1279R

5/8 inch (15.9 mm)

3/8 inch (9.5 mm)

RFK2379R

3/4 inch (19 mm)

1/2 inch (12.7 mm)

REFRIGERANT CHARGE DATA

This information is subject to change without notice.  

Refer to machine data/serial plate for accurate information. 

Information relating to R404A refrigerant reflects older 

Manitowoc Flake & Nugget machines - R452A can be used as 

a replacement for R404A providing correct charge values are 

used.

Model

R404A (kg)

R452A (kg)

R290 (kg)

Air-

cooled

Water-

cooled

Air- 

cooled

Water- 

cooled

Air- 

cooled

Water- 

cooled

UF0244

0.245

0.190

0.245

0.190

0.095

0.090

UF0200

0.245

0.190

0.245

0.190

0.095

0.090

UN0200

0.210

0.190

0.220

0.210

0.090

---

UF0350

0.320

0.200

0.370

---

---

---

UN0300

0.350

0.230

0.400

0.230

0.130

---

UF0388

0.320

0.200

0.360

0.200

0.115

0.130

UF0399

0.320

0.200

0.370

0.200

0.115

0.130

RF0320

0.335

0.220

0.370

0.220

0.148

---

RN0320

0.440

0.220

0.550

0.235

0.140

---

RF0620

0.550

0.450

0.550

0.450

0.140

---

RN0620

0.550

0.450

0.550

0.450

0.140

---

RF1300

0.720

0.510

0.800

0.510

0.145

---

RN1100

0.720

0.510

0.660

0.510

0.145

---

RF2500

1.800

1.100

1.800

---

---

---

Condensers

RJC0875 

RJC1275

1.200

---

---

---

---

---

RJC2375

2.500

---

---

---

---

---

RJC4875

Data Is Not Currently Available

Important

Manitowoc remote systems are only approved and 

warranted as a complete new package. Warranty on the 

refrigeration system will be void if a new ice machine 

head section is connected to pre-existing (used) tubing or 

condensing units or vice versa.

USAGE WITH NON-MANITOWOC CONDENSING UNITS

Manitowoc Remote Condensing Units are specifically 

designed for usage with a QuietQube® Ice Machine Head 

Section. Standard condensing units and Non-Manitowoc 

condensing units are not approved for use with a 

QuietQube® Ice Machine Head Section.

,

Caution

The 60-month compressor warranty (including the 

36-month labor replacement warranty) will not 

apply if the Manitowoc Ice Machine and Manitowoc 

Remote Condensing Unit are not installed according 

to specifications. This warranty also will not apply if 

the refrigeration system is modified with a condenser, 

heat reclaim device, or other parts or assemblies not 

manufactured by Manitowoc Ice.

Factory Equipment Refrigeration Amounts

ICE MACHINE HEAD SECTION
Each ice machine condensing unit ships from the factory 

with a R-404A refrigerant charge appropriate for the entire 

system operation. The serial tag on the ice machine indicates 

the refrigerant charge. The refrigerant charge is sufficient to 

operate the ice machine in ambient temperatures between 

-29°C and 4.9°C. With line set lengths of up to 30.5 m.
REFRIGERATION LINE SETS/TRAP KIT
Refrigeration Rated Tubing and Trap Kits are shipped capped 

with atmospheric pressure.

Summary of Contents for Manitowoc RCUF1200

Page 1: ...umber 000016034 Rev 00 07 19 Flake and Nugget Model Ice Machines UFK UNK RFK RNK Installation Operation and Maintenance Manual Original Document Caution Read this instruction before operating this equ...

Page 2: ......

Page 3: ...perly trained technicians aware of the dangers of dealing with high voltage electricity and refrigerant under pressure The technician must also be certified in proper refrigerant handling and servicin...

Page 4: ...des and stability requirements Remove all removable panels before lifting and installing and use appropriate safety equipment during installation and servicing Two or more people are required to lift...

Page 5: ...e components obtained from the equipment manufacturers authorized replacement part network This equipment must be installed in accordance with the ASHRAE 15 Safety Standard for Refrigeration Systems T...

Page 6: ...f the appliance by a person responsible for their safety Do not allow children to play with clean or maintain this appliance without proper supervision n Warning Follow these precautions to prevent pe...

Page 7: ...h the authority having jurisdiction Turn off and lockout all utilities gas electric water according to approved practices during maintenance or servicing Units with two power cords must be plugged int...

Page 8: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Page 9: ...nections 14 Cooling Tower Applications 14 Ice Machine Water Usage 14 Water Supply and Drain Line Sizing Connections 15 Electrical Service 16 Voltage 16 Fuse Circuit Breaker 16 Ground Fault Circuit Int...

Page 10: ...on 24 RN0620 RF0620 RN1100 RF1300 RF2500 RF1220 RF2200 Operation 24 Section 4 Maintenance Interior Cleaning and Sanitizing 25 Cleaning Sanitizing Procedure 25 Heavily Scaled Cleaning Procedure 25 Exte...

Page 11: ...RNK1100A RNP100A RNK100W RNF1020C RCUF1200 Flake Modular Models Self Contained Air Cooled Self Contained Water Cooled Rack Unit Head Section QuietQube Head Section RCU Remote Condensing Unit RFK0320A...

Page 12: ...quick and easy way to protect your investment Scan the QR code with your smart device or enter the link in a web browser to complete your warranty registration WWW MANITOWOCICE COM SERVICE WARRANTY WA...

Page 13: ...e ice machine and bin must be level Install the bin drain and ice machine drain separately Ice machine drain must be vented Bin drain termination must have an air gap When local code requires a backfl...

Page 14: ...r cooled condenser drain lines Insulate them to prevent condensation Vent the ice machine drain to the atmosphere The ice machine drain requires an 46 cm vent Do not vent the condenser drain on water...

Page 15: ...ater Inlet 3 32 C 138 1034 kPA 3 8 FPT RF2500 1 2 FPT Condenser Water Drain 1 2 MPT Bin Drain 3 4 FPT Large Capacity Bin Drain 1 FPT UNDERCOUNTER UNITS ROUTE DRAIN TUBING TO OPEN SITE DRAIN WATER SHUT...

Page 16: ...separate fuse circuit breaker are required for each ice machine GROUND FAULT CIRCUIT INTERRUPTER We do not recommend the use of a GFCI GFI circuit protection with our equipment If a GFCI GFI is requi...

Page 17: ...A N A UN0300 230 1 50 10 Amp N A 3 3 N A N A UF0388 230 1 50 10 Amp N A 3 3 N A N A UF0399 230 1 50 10 Amp N A 3 3 N A N A RF0320 230 1 50 20 Amp 12 8 N A N A N A RN0320 230 1 50 20 Amp 12 8 N A N A...

Page 18: ...0 0 145 RF2500 1 800 1 100 1 800 Condensers RJC0875 RJC1275 1 200 RJC2375 2 500 RJC4875 Data Is Not Currently Available Importan Manitowoc remote systems are only approved and warranted as a complete...

Page 19: ...ed personnel are required for proper rigging and lifting Step 1 Verify Ice Machine and Remote Condensing Unit Locations Are Within Guidelines Prior to installation of the ice machine head section and...

Page 20: ...he ice machine head section or the remote condensing unit Step 4 Connecting the line set To prevent oxidation of the copper purge line set and condensing unit with dry nitrogen while brazing A Connect...

Page 21: ...ned before operating the ice machine A Backseat open turn counterclockwise the suction line shutoff valve B Backseat open turn counterclockwise the liquid line shutoff valve Verify suction and liquid...

Page 22: ...ice making water turned on Are all electrical leads free from contact with refrigeration lines and moving equipment Has the owner operator been instructed regarding maintenance and the use of Manitow...

Page 23: ...3 6 RN0620 3 RF0620 3 RN1100 3 RFF1300 4 RF1220 3 RF2500 3 RF2200 3 1 2 3 4 5 6 7 1 2 3 4 5 6 7 BIN THERMOSTAT SMALL NUMBERS LESS ICE IN BIN LARGE NUMBERS MORE ICE IN BIN EVAPORATOR LOW TEMPERATURE SA...

Page 24: ...lb C The water reservoir is full of water Placing the toggle switch in the ON position starts the gear motor and a 10 minute compressor time delay The compressor starts and the float valve controls th...

Page 25: ...fter this procedure Exterior Cleaning Remove dust and dirt off exterior surfaces with mild household dishwashing detergent and warm water Wipe dry with a clean soft cloth Cleaning Sanitizing Procedure...

Page 26: ...witch opens Step 16 After all of the sanitizer water solution has been added to the reservoir turn on the ice making water supply Step 17 Continue the freeze cycle for 30 minutes and then discard all...

Page 27: ...brush or sponge NOT a wire brush to carefully clean the parts 5 Use the solution and a brush or sponge to clean all disassembled components and the inside of the bin 6 Rinse all cleaned parts with cle...

Page 28: ...and sanitize the ice machine 2 Press the power button and turn off the ice machine 3 Turn off the water supply disconnect and drain the incoming ice making water line at the rear of the ice machine an...

Page 29: ...n thermostat open or ice touching thermostat probe Adjust thermostat or remove ice No water in reservoir No water to ice machine plugged filter float valve defective Ice chute switch open Check for ic...

Page 30: ...30 Part Number 000016034 Rev 00 07 19 Troubleshooting Section 5 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 31: ......

Page 32: ...s and premier chain operators or growing independents with industry leading equipment and solutions Our cutting edge designs and lean manufacturing tactics are powered by deep knowledge operator insig...

Reviews: