5. Operation
Page 34
104781 - MRF-2 | MRH-2 - V2.4 - 22.07.2020
Description
Range
Default
P65
P66
P67
P68
P69
P70
P71
P72
Min. adjustable value für hysteresis 1 below
Max. adjustable value für hysteresis 1 up
Min. adjustable value für hysteresis 2 below
Max. adjustable value für hysteresis 2 up
Min. adjustable value für hysteresis 3 below
Max. adjustable value für hysteresis 3 up
Min. adjustable value für hysteresis 4 below
Max. adjustable value für hysteresis 4 up
0,1K .. 99,9 K
0,1K .. 99,9 K
0,1K .. 99,9 K
0,1K .. 99,9 K
0,1K .. 99,9 K
0,1K .. 99,9 K
0,1K .. 99,9 K
0,1K .. 99,9 K
0,1
10
0,1
10
0,1
10
0,1
10
Limiting the setting of parameters C20 .. C23
P75
Switch-on delay relay X
0 .. 5
0
Used to determine whether a relay (and if so which) should be switched on with a delay.
For delay time see [P76].
0
= disabled
1 .. 5
= applies to relay 1..5
P76
Time setting for switch-on delay
0 .. 999 sec.
0
P77
Switch-off delay relay X
0 .. 5
0
Used to determine whether a relay (and if so which) should be switched off with a delay.
For delay time see [P78].
0
= disabled
1 .. 5
= applies to relay 1..5
P78
Time setting for switch-on delay
0 .. 999 sec.
0
P80
P81
P82
P83
P84
P85
P86
P87
P88
P89
Minimum duty relay K1
Minimum off time relay K1
Minimum duty relay K2
Minimum off time relay K2
Minimum duty relay K3
Minimum off time relay K3
Minimum duty relay K4
Minimum off time relay K4
Minimum duty relay K5
Minimum off time relay K5
0 .. 999 sec.
0 .. 999 sec.
0 .. 999 sec.
0 .. 999 sec.
0 .. 999 sec.
0 .. 999 sec.
0 .. 999 sec.
0 .. 999 sec.
0 .. 999 sec.
0 .. 999 sec.
0
0
0
0
0
0
0
0
0
0
P91
P92
2-lead / 3-lead setting for sensor 1
2-lead / 3-lead setting for sensor 2
2 .. 3
2 .. 3
2
2
2: 2 lead
3: 3 lead
P95
Mutual switch-on delay for control components
0 .. 999 sec.
0
P96
Switch-on delay for control components after
mains power on
0 .. 999 sec.
0
P98
Button lock C parameters
0 .. 1
0
0: not locked
1: locked