Installation and operating instruction
Oil burner WL40Z-A
7 Commissioning
83298002 3/2019-11 La
49-112
Preset P
1
Press [+] key.
Factory setting operating point P
1
(stage 1) is displayed.
Press and hold [L/A] key and set air damper setting determined using the [–] or
[+] key [ch. 7.1.3].
Press [Enter] and [L/A] simultaneously.
Factory setting fan speed (
100
%) is displayed.
Preset P
0
Press [+] key.
Factory setting operating point P
0
(ignition position) is displayed.
Press and hold [L/A] key and set the same values as for P
1
using the [-] or [+]
key.
Press [Enter] and [L/A] simultaneously.
Factory setting fan speed (
100
%) is displayed.