Installation and operating instruction
Oil burner WL40Z-A
7 Commissioning
83298002 3/2019-11 La
40-112
7.1.3 Setting values
Set mixing head relative to the combustion heat rating required. For this, the dif-
fuser setting and the air damper setting should be matched.
Determine diffuser setting and air damper setting
Do not operate the burner outside of the capacity graph.
Determine the diffuser setting (dimension X) and air damper setting required
from the diagram and note down.
Example
Burner capacity stage 2 / stage 1 required
450 kW / 247.5 kW
Diffuser setting (dimension X)
21.8 mm
Air damper setting stage 2 / stage 1
78° / 38°
Diffuser default settings
2
1
10
12
14
16
18
20
22
24
26
8
6
4
100 125
175
225
275
325
375
425
475
525
575
150
200
250
300
450
350
500
550
400
1
Combustion heat rating [kW]
2
Diffuser settings (dimension X) [mm]
Air damper default settings
2
1
4
3
40
50
60
70
80
90
30
20
100 125
175
225
275
325
375
425
475
525
575
150
200
300
350
500
550
400
250
450
1
Combustion heat rating [kW]
3
Stage 1
2
Air damper setting [°]
4
Stage 2