
Installation and operating instruction
Oil burner WL40Z-A
7 Commissioning
83298002 3/2019-11 La
43-112
Preset P
1
Press [+] key.
Factory setting operating point P
1
(stage 1) is displayed.
Press and hold [L/A] key and set air damper setting determined using the [–] or
[+] key [ch. 7.1.3].
Preset P
0
Press [+] key.
Factory setting operating point P
0
(ignition position) is displayed.
Press and hold [L/A] key and set the same values as for P
1
using the [-] or [+]
key.
Preset P
2
and P
3
Press [+] key.
Factory setting operating point P
2
(switch off point stage 2 when running
closed) is displayed.
Press and hold [L/A] key and set P
2
approx. 3 … 8° above P
1
using the [–] or
[+] key.
Press [+] key.
Factory setting operating point P
3
(switch on point stage 2 when running open)
is displayed.
Press and hold [L/A] key and set the same values as for P
2
using the [-] or [+]
key.
Press [+] key.
Combustion manager is preset.