Part number 550-142-058/0811
89
WM97+
gas
-
fired
water
boiler
—
Boiler Manual
Display
Condition
Diagnostics
Corrective Action(s)
BLOWER FAULT
Blower unable to reach
required speed or does not
reach 0 RPM when turned off.
NOTICE: The blower will not
rotate without a low voltage
signal. Unplugging the low
voltage blower wire harness
will not allow or cause the
boiler to rotate.
Reset using manual reset screen
on display; control module will
check again after 1 hour and will
automatically restart if condition
is corrected
Check wire harness for loose connections and pin engagement at blower
connections, chassis mount connection through control housing, and
control module. Unplug connection at blower and at control module
and check continuity between ends. Blower is connected to both low
voltage and line voltage harness.
Check Diagnostics - Inputs screen with boiler in standby mode and
blower not running. If BLOWER SPEED is not 0 RPM then replace blower.
If blower does not rotate during ignition sequence check for 120V power
at blower connection. If 120Vac power at blower motor and it doesn't
start replace blower. Check power at control module. If 120Vac is not
present at control module when boiler is powered replace control
module. Refer to repair parts section.
IGNITION
FAULT
Boiler went through 5 ignition
attempts and never detected
flame
Automatically resets after 1 hour
or can be reset by performing
manual reset on boiler.
Check condensate trap for blockage allowing condensate to accumulate
inside heat exchanger.
Check ignition cable connection.
Fouled, worn, bent, or faulty igniter.
Fouled igniters can be cleaned for additional use with fine grit sand
paper or steel wool.
Worn or badly fouled igniters should be replaced with the proper repair
part.
Igniter rods should be parallel with a 3.5mm (0.138in) spark gap.
Dirty burner and/or heat exchanger will cause high back pressure and
poor ignition. Follow procedure in maintenance section of this manual
to clean burner and heat exchanger using flue cleaning tool and rinse
method.
Visual inspection of flueways will often will not be able to diagnose
condition.
Check combustion settings on high and low fire and adjust per setup
instructions if necessary.
Check incoming gas pressure with boiler off and at high fire. Adjust
within limits on rating label.
Verify correct boiler model is selected in control and high altitude is
selected for installations 5500ft above sea level.
Check ignition cable resistance. Should measure 1000 Ohms (+/- 50
Ohms)
Check for flue pipe and intake pipe restrictions or blockage
Check burner fasteners and gaskets
Check venturi gaskets and proper propane orifice bushing
Check condensate trap for blockage allowing condensate to accumulate
inside heat exchanger
Troubleshooting
(continued)
Figure 88 Troubleshooting suggestions for WM97+ boilers —
Fault displays, diagnostics and corrective actions
(cont.)