Boiler Manual
Troubleshooting
(continued)
Figure 88
Troubleshooting suggestions for WM97+ boilers —
Control module Error Condition Log
The control module is able to record information about the boiler’s condition at the time of the three previous faults or errors. This
information is available to view in Contractor Menus under “DIAGNOSTICS” by selecting “ERRORS.” The control will display
the following information:
Information
Description
Action
Control Fault
Records the number of internal control faults
Select and press the enter key to reset this count
Ignition Retries
Displays the number of ignition attempts in the current
ignition sequence.
Manual Reset Count
Records number of lockouts that required a manual reset
since this count was last cleared.
Select and press the enter key to reset this count
Auto Reset Count
Records number of lockouts that have automatically reset
since this count was last cleared.
Select and press the enter key to reset this count
Lockout History 1
Details of present or last recorded lockout
Select and press the enter key for more details
Lockout History 2
Details of boiler during the second oldest lockout still in
memory
Select and press the enter key for more details
Lockout History 3
Details of boiler during the oldest lockout still in memory
Select and press the enter key for more details
How to read the last 3 lockout histories:
1.
Scroll down to “DIAGNOSTICS” and press the
enter key (Square Key in center)
2.
Scroll down to “ERRORS” and press the enter key
(Square Key in center)
3.
Scroll down to “LOCKOUT HISTORY #” and press
the enter key.
4. Scroll to choose the either “MANUAL RESET” or
“AUTO RESET” and press the enter key to display
the fault condition that was recorded.
5.
Press the left arrow key to return to the LOCKOUT
HISTORY # screen. Scroll up or down to highlight
other choices and press the enter key to view the
details of the boiler’s condition when the lockout
was recorded.
How to clear all lockout histories:
1.
While on the “ERRORS” screen, hold the Left
and Right arrow buttons simultaneously for 7
seconds.