Part number 550-142-085/0712
WM97+
gas
-
fired
water
boiler
—
Boiler Manual
– 44 –
Figure 49
WM97+70/110
Zone valve zoning —
primary/secondary connection —
a system circulator is required
System piping
(continued)
Legend — Figure 49
1
WM97+70 or 110 boiler
2
Indirect water heater, if used
(for CWH installations, refer
to the Weil-McLain CWH
manual)
3
Relief valve, supplied with
boiler, field piped — MUST
be piped to boiler supply
connection — see page 13 for
information
4
Relief valve piping to drain —
see page 37
5
DHW circulator
6
Isolation valves
7
System circulator
8
Supplementary expansion
tank, diaphragm type, if used
9
Air separator
10
Flow/check valves
11
Purge/drain valves (one drain
valve is supplied loose with
the boiler)
12
Boiler circulator, with inte-
gral flow/check valve, factory
installed in boiler
13
Zone valves
14
Primary/secondary by-
pass valve — see page 38 for
information — OPEN: Boiler
connected as primary/second-
ary
20
Make-up water supply
21
By-pass pressure regulator,
RECOMMENDED for zone
valve systems unless other
provision is made
23
Backflow preventer, if used
25
Pressure reducing valve, if
used
26
Internal expansion tank,
diaphragm-type
27
Quick-fill valve, if used
28
DHW boiler water supply
connection, when used — see
page 13 for information
29
DHW boiler water return
connection, when used — see
page 13 for information
30
Pressure/temperature
gauge, supplied with boiler,
field piped
31
Heating circuits
32
Additional heating circuits, if
any
= Items supplied with boiler
— all other items supplied by
installer
Use isolation relays if connected 3-wire zone valve end
switches to the WM97+ control inputs.
Connect zone valve end switches to ZONE 2 input.
Connect system circulator to CIRC 2 output.
DHW refers to an indirect-fired domestic hot
water storage tank. CWH refers to a Weil-
McLain Companion Water Heater.
ZONE VALVE zoning — primary/secondary
Internal P/S by-pass valve OPEN
WM97+70 or 110 only
The boiler primary/secondary by-pass valve
MUST be OPEN
to prevent excessive head caused by running the boiler circula-
tor and system circulator in series.
See Figure 49.
1. This configuration is for WM97+70 or 110 zone valve systems that need
more flow than the boiler’s circulator can provide (see page 43 for infor-
mation).
2.
OPEN
the boiler internal primary/secondary by-pass valve.
3. Install a system circulator (supplied by installer) as shown.
4. A benefit of primary/secondary piping is that it does not apply the head of
the boiler circulator to the system zone valves.
Supplementary expansion tank, if used
1. Connect the supplementary expansion tank and make-up water piping as
shown in Figure 43, page 40.
2. DO NOT use a closed-type tank if connecting to a water heater that is
equipped with an automatic air vent.
DHW or CWH, if used
1. DHW or CWH direct connection — Pipe from the boiler’s bottom con-
nections to water heater boiler connections as shown. See CWH manual
for CWH piping instructions.
2. DHW as a zone — A DHW tank can be piped as a zone if a DHW tank or
CWH is
NOT
connected to the boiler. To provide DHW priority operation
in this case, a Weil-McLain WMZV must be used.
3. Priority option — By default, the WM97+ control turns off space heating
to its Zone 2 and Zone 3 outputs during domestic water heating on Zone 1.
The MAX ON TIME setting can be adjusted to limit how long this occurs.
Set the MAX ON TIME to “0” to disable domestic priority.
4. If
NOT
connecting a water heater, terminate the bottom connections as
shown in the inset on Figure 49.
Controlling the zones
1. The WM97+ control can be set up to operate on space heating only or on
space heating plus DHW or CWH. Refer to Field wiring, beginning on
page 62, for instructions on wiring to zone valves.
2. The boiler and zone valves can also be operated by a Weil-McLain WMZV
zone controller.