Part number 550-143-010/1021
84
GV90+
series
2
gas-fired water boiler – boiler manual
CHART 2
TSTAT/CIRC & POWER lights flashing
Electrical shock hazard
— Wherever you see TURN OFF POWER, follow the instructions. Failure to fol
-
low instructions could result in severe personal injury, death or substantial property damage.
Is return water temperature sensor clamped
securely to the return pipe in the boiler?
Yes
No
•
Remove
CIRCULATORS
from plug receptacle of IBC.
•
Place voltmeter leads across the right-side
120VAC N
and
120VAC H
pins of the
CIRCULATORS
receptacle.
Does the voltmeter indicate 120 VAC?
No
Yes
Is boiler internal Bypass circulator operating?
No
Yes
•
Test wire continuity of
circulator wire harness.
Is harness ok?
No
Yes
•
Check the boiler internal return pipe where it enters the
boiler sections. The
TSTAT/CIRC
and
POWER
lights
will flash after 30 minutes as long as the return water
temperature is less than 130 °F.
•
Wait up to 20 minutes to give the boiler and system a
chance to respond.
Does problem persist?
No
Yes
•
Attach sensor to pipe with clamp provided.
•
Follow return temperature sensor checking procedure
on
. Replace sensor if necessary.
•
Retest.
•
Check for stray voltage on the incoming thermostat wires.
Disconnect the two external wires connected to the boiler
thermostat wires.
•
Connect a voltmeter across the two incoming wires. Close each
thermostat, zone valve and relay in the external circuit one at a
time and check the voltmeter reading across the wires. There
should NEVER be a voltage reading. If a voltage does occur
under any condition, check and correct the external wiring.
(This is a common problem when using 3-wire zone valves.)
•
Once the external thermostat circuit wiring is checked and cor
-
rected if necessary, reconnect the external thermostat circuit
wires to the boiler thermostat wires and allow the boiler to cycle.
Did you find and correct a voltage across the two external thermostat circuit wires?
Yes
No
•
Boiler should now operate per the normal sequence of op
-
•
Replace the IBC.
•
Retest.
•
Boiler may now be operating normal
-
ly. Verify against normal sequence of
•
If boiler appears not to be heating, troubleshoot boiler
per
CHART 7
, page 89. If problem cannot be resolved,
replace water temperature sensor and retest. Then
replace IBC if sensor does not correct the problem.
•
If boiler is heating, but the temperature at the return
pipe does not increase above 130 °F, there may be an
incorrectly-piped external circulator forcing water through
the boiler. Check external piping and correct.
•
Replace circulator harness.
•
Retest.
•
Reconnect circulator harness to IBC.
•
Attempt to get the circulator started by giving it a sharp rap
on the end of the circulator motor (to release a possibly
locked impeller).
•
If the circulator begins to operate, allow it to operate for a few
minutes to see if the problem clears.
•
With harness connected and power to circulators, check for
120 VAC at circulator harness terminals. If no voltage is pres
-
ent with circulators under load. Replace IBC and retest.
•
If problem persists, replace the Bypass circulator.
•
Retest.
Troubleshooting
(continued)