background image

Part Number 550-141-807/0298

5

Flame Guardian WMBC-1A Electronic Pilot System – IRI

1. Size gas piping considering:

a. Diameter and length of gas supply piping.
b. Number of fittings.
c. Maximum gas consumption (including any possible future expansion).
d. Allowable pressure drop from gas meter outlet to boiler.  For pressure drops, see ANSI-Z223.1 – latest

edition.

2. Size natural gas piping from table below.  Size piping to provide proper inlet pressure to gas valve when operating

at rated input.
a. Inlet gas pressure to manual main shutoff gas valve minimum 7” W.C. standard (5½” on special order) –

maximum 13” W.C.

b. If pressure to gas valve exceeds 13” W.C., install positive dead-end lockup gas pressure regulator up stream of

hand valve.

c. To obtain approximate cubic feet per hour, divide input (BTU/HR) by 1000.

3. Remove gas supply knockout disc from jacket panel.
4. Follow good piping practices.
5. Pipe joint compound (pipe dope) must be resistant to corrosive action of liquefied petroleum gases.  Apply

sparingly only to male threads of pipe joints.

6. Install drip leg at inlet of gas connection to boiler.  Where local utility requires, extend drip leg to floor.
7. Install ground joint union when required for servicing.
8. Support piping by hangers, not by boiler or its accessories.
9. Purge all air from supply piping.
10. Check all connections for leaks.

a. Close manual main shutoff valve during any pressure testing at less than 14.0 inches water column.
b. Disconnect boiler and gas controls from gas supply piping during any pressure test greater than 14.0 inches

water column.

11. Set gas pressure switches as follows or to local inspector’s requirements:

a. Low – 3.0” W.C.

b.    High – 14.0” W.C

II

Gas piping

Do not check for gas leaks with an open flame – BUBBLE TEST.  Failure to use bubble test or test for leaks can cause
severe personal injury, death or substantial property damage.

III

Wiring

1. All wiring must be installed in accordance with the requirements of the National Electrical Code and any additional

national, state or local code requirements having jurisdiction.  All wiring must be N.E.C. Class 1.

2. The boiler must be electrically grounded in accordance with the National Electrical Code, ANSI/NFPA No. 70-

latest edition.  Use 105 °C. thermoplastic wire, or equivalent, if any of the original wire must be replaced (except
for pilot spark, sense and ground wires).

3. Supply wiring to the boiler must be No. 14 gauge or heavier.  Install in conduit.
4. A separate electrical circuit with a fused disconnect switch (15 amp. recommended) should be used for the boiler.

For your safety, turn off electrical power supply before making any electrical connections to avoid possible electrical
shock hazard.

Table 2

Natural gas

supply pipe

sizing

PIPE
SIZE

10’

20’

30’

40’

50’

75’

100’

150’

1¼"

1,050

730

590

500

440

360

305

250

1½"

1,600

1,100

890

760

670

545

460

380

2"

3,050

2,100

1,650

1,450

1,270

1,020

870

710

2½"

4,800

3,300

2,700

2,300

2,000

1,650

1,400

1,130

3"

8,500

5,900

4,700

4,100

3,600

2,900

2,500

2,000

4"

17,500

12,000

9,700

8,300

7,400

6,000

5,100

4,100

* Include measured length of gas supply piping and allowance in feet for number and size of fittings.

PIPE LENGTH, FEET (NATURAL GAS CAPACITIES, LISTED IN MBH)
(Specific Gravity 0.60 @ Pressure Loss of 0.30" w.c.)

Summary of Contents for FLAME GUARDIAN WMBC-1A

Page 1: ...ds that can cause severe personal injury death or substantial property damage Indicatesspecialinstructionsoninstallation operationormaintenancethat are important but not related to personal injury or...

Page 2: ...ain recommends installing manual controls in addition to standard as required by local inspector Refer to the LGB Boiler Manual Boiler Controls section a Steam boilers require a manual reset Low Water...

Page 3: ...WMBC Panel Terminal G2 Ground Terminal Pilot Mounting Bracket 10 32 x 1 4 Machine Screws 2 Main Burner with Pilot Mounting Bracket Compression Union Sensor Lead Burner Support Bar Pilot Line Tubing I...

Page 4: ...d gas valve w on off actuator 5 Pilot gas pressure regulator 6 Normally open solenoid vent valve 7 Pilot solenoid gas valve 8 Test cock 10 Manual leak checking gas valve 11 Regulating diaphragm gas va...

Page 5: ...during any pressure test greater than 14 0 inches water column 11 Set gas pressure switches as follows or to local inspector s requirements a Low 3 0 W C b High 14 0 W C II Gas piping Do not check for...

Page 6: ...Part Number 550 141 807 0298 6 LGB Series2 ControlSupplement Part Number 550 141 807 0298 7 Flame Guardian WMBC 1A Electronic Pilot System IRI Figure 5 WMBC 1A panel wiring schematic...

Page 7: ...Part Number 550 141 807 0298 8 LGB Series2 ControlSupplement Figure 6 WMBC 1A panel wiring diagram factory wiring...

Page 8: ...Part Number 550 141 807 0298 9 Flame Guardian WMBC 1A Electronic Pilot System IRI Figure 7 WMBC 1A field wiring diagram...

Page 9: ...1 2 W C 6 Turn off boiler 7 Remove manometer from manifold and plug the tapping 8 Reconnect the blue wire in the two stage gas valve junction box 9 Turn on electrical power supply and gas supply to b...

Page 10: ...d trial for main flame Yellow pilot on lamp goes out 6 Main flame sensor proves main burner operation at low fire 7 Flame safeguard control energizes downstream gas valve to high fire through firing r...

Page 11: ...415 Pilot Burner Honeywell Q179C1009 511 330 181 Pilot Bracket Weil McLain 460 005 624 Main Flame Sensor Honeywell 392956 511 724 274 Main Flame Sensor Bracket Weil McLain 423 300 420 Main Burner with...

Reviews: