background image

Part number 550-101-232/0703

13

 

GAS

-

FIRED

 

WATER

 

BOILER

 — 

Installation Manual —  Multiple-boiler Systems

Figure 12

Manifolding combution air piping

Combustion air & vent piping installation

Vent piping

1. Each boiler requires an individual vent pipe, in-

stalled and terminated per the Ultra Boiler Manual
and Ultra Boiler Venting Suppments.

2. The vent pipes of multiple boilers must terminate on

the same side of the building as their air inlet piping,
and per all requirements of the Ultra Boiler Manual
and Vent Supplements.

Combustion air piping

1. Provide combustion air piping to each boiler, fol-

lowing all requirements for installation and termi-
nation per the Ultra Boiler Manual and Ultra Boiler
Venting Supplements.

2. Combustion air piping can be supplied from a

common combustion air manifold, installed and
terminated as shown in Figure 12, below.

Combustion air manifolds

1. When combustion air supplied from a common air

manifold pipe as in Figure 12, size the common air
duct and louver free area from the minimum free
area given in Figure 1, pages 4 and 5.

2. All joints must be sealed.

3. The air inlet must be located:

at least 3 feet below any vent located within 10
feet.

the louver bottom must be 12 inches above grade
or above the snow line.

4. Compensate for louver blockage when calculating

free air openings. Refer to manufacturer’s instruc-
tions for size. If unknown use:
a. Wood louvers — 20-25% free area.
b. Metal louvers or grilles — 60-75% free area.

5. Lock open louvers or interlock with boiler controls

to open automatically with boiler operation.

Summary of Contents for Boiler

Page 1: ...cluding this manual the Ultra Boiler Manual and all applicable Supplements Consider all connections to the boilers before selecting a location and layout Failure to comply could result in severe personal injury death or substantial property damage Part No 550 101 232 0703 Gas fired water boiler Installation Manual with Multiple boiler systems with Weil McLain Easy Fit piping ...

Page 2: ...tion 7 Easy Fit Piping Easy Fit Piping installation 8 Piping schematic 9 Easy Fit Piping 3 dimensional drawing 10 Easy Fit Piping 4 boilers 3 water heaters 3 dimensional 11 Easy Fit Piping with isolation exchanger 3 dim drawing 12 Combustion air and vent piping installation Vent piping 13 Combustion air piping 13 Combustion air manifolds 13 Gas piping Connecting gas supply piping 14 Common gas pip...

Page 3: ...allation on combustible flooring not carpet 3 Ultra boilers are tested for 30 P S I working pressure higher pressure not available 4 For systems requiring greater than 30 P S I relief valve setting install a heat exchanger to isolate the boilers from the main system See page 12 for suggested piping 5 Maximum operating temperature of each boiler is 190 F This manual provides general guidelines for ...

Page 4: ...Part number 550 101 232 0703 4 GAS FIRED WATER BOILER Installation Manual Multiple boiler Systems Ratings and engineering data Figure 1 Ratings and engineering data see page 5 for notes D O E ...

Page 5: ...ions see Figure 4 page 7 4 Operating weight is the total weight including water 5 Ultra 230 boilers can be vented with 3 inch vent instead of 4 inch with the limitations described in the Ultra Boiler Vent Supplement Using the smaller vent pipe reduces maximum allowable run All Ultra installations require a separate vent pipe and termination for each boiler Vent piping cannot be manifolded Install ...

Page 6: ...ping and gas pipe can be routed through bottom of enclosure using wall mounting kit Dimensions Figure 2 Dimensional data 2 Boilercirculatorisshippedloose Mount boiler circulator in connecting piping as shown in this manual Boiler is shipped with 1 and 1 circulator flanges 3 Relief valve is shipped loose See Boiler Manual pages 14 and 15 for mounting details Relief valve mounts on street elbow conn...

Page 7: ...alkline boiler locations on foundation or boiler room floor 5 Uncrate assemble and mount boilers according to Ultra Boiler Manual 6 Provide clearance for installa tion of venting air piping gas piping expansion tank primary circulator and other accessories Wall mounting 1 Ultra boilers may be wall mounted following the instruc tions in the Ultra Boiler Manual and the Wall Mounting Supple ment 2 Wh...

Page 8: ...tem flowing left to right reverse the locations of the Manifolds accordingly 4 Connect from Easy Fit Manifold branches to boiler supply and re turn connections using 1 nominal copper tubing or steel pipe maxi mum run 15 5 Provide a flow check valve in the supply piping of each boiler as shown in piping diagrams in this manual Install an isolation valve on the supply and return of each boiler as sh...

Page 9: ...d by applicable codes 12 Isolation valve 13 Cold water supply 14 Supply water temperature control when used 15 Low water cutoff when used place above primary header 16 Water flow switch when used 17 Boiler circulator each boiler 18 System supply 19 System return 20 Boiler relief valve and discharge piping installed per Ultra Boiler Manual This manual provides general guidelines for piping and inst...

Page 10: ...ach boiler 2 Isolation valves when used 3 Caps 4 Easy Fit Manifold supply sized per Fig 6 or Fig 7 page 8 5 Easy Fit Manifold return sized per Fig 6 or Fig 7 page 8 6 Primary circulator 7 Expansion tank diaphragm type 8 System air eliminator 9 System automatic air vent 13 Cold water supply 17 Boiler circulator each boiler 18 System supply 19 System return 20 Boiler relief valve and discharge pipin...

Page 11: ... check valves to prevent induced or gravity flow in heating system or DHW piping 28 Check valve to prevent heat migration in heating system 29 See water heater manual for DHW piping The DHW piping must also be manifolded together since the boiler side piping is manifolded If DHW heaters supply separate DHW circuits provide an individual circulator for each water heater and control each circulator ...

Page 12: ...zed per Fig 6 or Fig 7 page 8 6a Heating system circulator exchanger tubeside 6b Heat exchanger shellside circulator 7 Expansion tanks diaphragm type 8 System air eliminator 9 System automatic air vent 13 Cold water supply connections 17 Boiler circulator each boiler 18 Heating system supply 19 Heating system return 20 Boiler relief valve and discharge piping installed per Ultra Boiler Manual Note...

Page 13: ...r Manual and Ultra Boiler Venting Supplements 2 Combustion air piping can be supplied from a common combustion air manifold installed and terminated as shown in Figure 12 below Combustion air manifolds 1 When combustion air supplied from a common air manifold pipe as in Figure 12 size the common air duct and louver free area from the minimum free area given in Figure 1 pages 4 and 5 2 All joints m...

Page 14: ... w c Do not check for gas leaks with an open flame use bubble test Failure to use bubble test or check for gas leaks can cause severe personal injury death or substantial property damage 6 Use pipe dope compatible with propane gases Apply sparingly only to male threads of pipe joints so that pipe dope does not block gas flow Failure to apply pipe dope as detailed above can result in severe persona...

Page 15: ... from Table 2 5 Refer to page 14 of this manual and to the Ultra Boiler Manual for testing gas piping 1 Construct gas header for multiple boilers using Figure 14 and the sizing tables below Refer to the National Fuel Gas Code for other conditions 2 Provide manual shutoff gas valve and ground joint union as shown in Figures 13 and 14 for each boiler When gas line en ters from top of the boilerl the...

Page 16: ...alysis and recommendations Initial fill water may contain enough minerals to produce damaging deposits Additional untreated makeup water will increase scale buildup Contamination may also come from scale and rust buildup inside the piping and heat distribution units of an older boiler system replaced with small multiple boiler units The result can lead to loss of efficiency and component failure 1...

Reviews: