Part number 550-100-168/0516
80
SlimFit
®
Series 3
COMMERCIAL
CONDENSING
GAS
-
FIRED
WATER
BOILER
—
Boiler Manual
&IGURE
$)!'./34)#3
menu details (continued) (see Figure 58, page 70 for access information)
DIAGNOSTICS menu
(continued)
-ENU)TEM
#OMMENT
2UN4IMES
"URNER4IME
Displays cumulative time the burner has been active (can be increased by user)
2OTATE4IME
Records the days of operation passed from the last time the Master boiler rotated the firing sequence.
)NPUT4IME
Displays cumulative time that Input 1 has been closed (Or 0-10V
t
1 volt)
)NPUT4IME
Displays cumulative time that Input 2 has been closed
)NPUT4IME
Displays cumulative time that Input 3 has been closed
.ETWORK4IME
Records time this boiler was running on a network call for heat generated by the Master boiler
)GNITION#OUNT
Displays total number of successful ignitions
-ASTER3HADOW
#OMM
"OILER)$
Displays boiler control type and ID number
,INKEDTO-ASTER
Shows if control is currently linked to a Master control
"OILERSON.ETWORK
Shows number of boilers currently on network
2EQUESTEDTO2UN
Shows if this control is being requested to satisfy a network call
4YPE
Shows whether the control is Network-P1, Network-P2, or NONE
2EQUESTED-OD2ATE
Rate coming from the Master
-AX"OILER4EMP
Displays maximum allowable boiler temperature
"OILER/N$IFF
Temperature differential from master boiler for network priorities
"OILER/FF$IFF
Temperature differential from master boiler for network priorities
.ETWORK"OILERS
&ORMULTIPLEBOILERSONLYn3EE3LIM&IT!DVANCEDMANUAL
Shows current rate of boiler
&
Shows Boiler Out temperature of boiler
Shows priority being satisfied, updated based on active demand
Shows system type of call for heat, updated based on active demand
/&
Shows the sequence position of that boiler in all the boilers available
",2
Shows boiler number this data belongs to
.ETWORK)NPUTS
"OILERNUMBER
Displays boiler number
)NPUTS
Displays input’s configuration and whether it is active. If input is active, it will be displayed in
BOLD
3OFTWARE6ERSIONS
Display
Software version of the microprocessor on the display circuit board
Main Micro
Software version of the main microprocessor on the control circuit board
Second Micro
Software version of the second microprocessor on the control circuit board
4/2%3%4
!,,()34/29
#/5.4%234/
:%2/
To reset all history counters to zero: Enter the DIAGNOSTICS menu. Then press and hold the left and right arrows
located below the control display. Hold for 5 seconds. This will cause ALL history to be deleted. To maintain
history, reset counters individually.
0!34%22/23
#ONTROL&AULT
Displays number of control faults
)GNITION2ETRIES
Displays cumulative ignition attempts. It is recommended that his be reset during yearly maintenance by holding down the
Left
and
Right
arrows or by selecting this line and pressing the
Enter
button
-ANUAL2ESET#NT
Displays number of manual reset lockouts since last cleared
!UTO2ESET#NT
Displays number of auto reset lockouts since last cleared
,OCKOUT(ISTORY
Choose this to view the most recent error recorded
&AULT.AME
Displays the name of the fault that occurred
&AULT4YPE
Displays the type of fault that occurred