![Weil-McLain 550 MBH Nstallation And Operation Manual Download Page 32](http://html1.mh-extra.com/html/weil-mclain/550-mbh/550-mbh_nstallation-and-operation-manual_952622032.webp)
Part number 550-100-168/0516
32
c. The vent pipe may run up as high as 4 feet, as shown in Fig-
ure 18 right side, with no enclosure. The vent pipe must be
secured with braces, and maintain all required clearances.
d. Space braces no further than 24 inches apart. (See WARNING
below for extremely cold climates.)
e. External venting greater than 4 feet requires an enclosure
around the vent pipe. The vent termination must exit through
the enclosure as shown in Figure 18, maintaining all required
clearances.
Do not exceed the maximum length of the outside vent
piping shown in Figure 18. Excessive length exposed to
the outside could cause freezing of condensate in the vent
pipe, resulting in potential boiler shutdown. In extremely
cold climates, install an insulated chase around the vent
piping, particularly when using longer lengths. The chase
must allow for inspection of the vent pipe, and insulation
must be protected from water.
&IGURE
DIRECT EXHAUST — Sidewall — configuration
options and minimum clearances
2. Consider the surroundings when terminating the vent:
a. Position the vent termination where vapors will not damage
nearby shrubs, plants or air conditioning equipment or be
objectionable.
b. The flue products will form a noticeable plume as they con-
dense in cold air. Avoid areas where the plume could obstruct
window views.
c. Prevailing winds could cause freezing of condensate and water/
ice buildup where flue products impinge on building surfaces
or plants.
d. Avoid possibility of accidental contact of flue products with
people or pets.
e. Do not locate the terminations where wind eddies could affect
performance, such as inside building corners, near adjacent
buildings or surfaces, window wells, stairwells, alcoves, court-
yards or other recessed areas.
&IGURE
DIRECT EXHAUST — Sidewall —
clearances to openings
&IGURE
DIRECT EXHAUST — Sidewall —
clearances from vent exit to forced air
intake
f. Do not terminate above any door or window or
under a deck. Condensate can freeze, causing ice
formations.
g. Locate or guard vent to prevent condensate damage
to exterior finishes.
3. Maintain clearances as shown in the illustrations in this
manual section. Also maintain the following:
a. Vent must terminate:
s
At least 6 feet from adjacent walls.
s
No closer than 5 feet below roof overhang.
s
At lease 3 feet above any forced air intake within
10 feet.
SlimFit
®
Series 3
COMMERCIAL
CONDENSING
GAS
-
FIRED
WATER
BOILER
—
Boiler Manual
DIRECT EXHAUST — Sidewall
(continued)