Operating Manual

Digital Multifunctional

Power Meter

with LED Display

- 3 -

679.B.101.03

Membrane key functions

 Select digit (lit decimal point)

 Increase rating or select menu

 Enter menu or accept changes

 Enter or leave device settings

Note:

 The device will react when releasing a button.

Reading out measured ratings

All measured ratings will be displayed for approximately 10 seconds one after the other.

To read out a particular measured rating, press the 

 key (repeatedly, if required).

The selected measured rating will then be displayed for approximately 10 seconds. After
that, the next measured rating in the order will be displayed.

Device Settings

On the device, the CT ratio can be set and the energy counters can be reset. For this
purpose the password must be entered.

In the meter settings, also data are shown which cannot be changed or which are not used:

PASS 00

Password

adjustable (see below)

nET 4Y

3-phase 4-wire system

not adjustable

PT 0001

Voltage transformer ratio

not adjustable

CT 0001

Current transformer ratio

adjustable (see below)

Adr 001

Address

not used

bAUd 9600

Baud rate

not used

CLEr no

Reset energy conters

adjustable (see below)

Entering the password (PIN)

The factory-set PIN is: 

01

 Enter device settings

 Select the 

PASS

 menu

 Select digit (lit decimal point)

 Adjust value

Adjust second digit in the same way, if necessary.

 Confirm