Entering CT ratio

The current transformer ratio CT must only be adjusted beetween 1 and 1999.

Example: With installed CTs 5000 A / 5 A, CT = 1000 must be adjusted.

 Enter device settings

Enter PIN (see page above)

 Select 

CT

 Enter the 

CT

 menu

 Select digit (lit decimal point)

 Adjust value

Adjust further digits in the same way, if necessary.

 Confirm

Note:

 Display may be wrong with a rated current of 5 A and a set CT ratio of more than

1999.

Resetting energy counters

 Enter device settings

Enter PIN (see page above)

 Select 

CLEr

 Enter the 

CLEr

 menu

 Adjust confirmation: 

no

 = No, 

YES

 = Yes

 Confirm

The energy counters are reset.

Display is set back from 

YES

 to 

no

.

Technical Data

Dimensions

Electrical connection

Bezel

 96 mm

Rated voltage

230/400 V

Bezel height

12 mm

Rated current

5 A

Panel cutout

 90

+0.5

 mm

Current connection

via CTs N/5 A

Weight

0.5 kg approx.

Auxiliary supply

85  ...  265  V  AC  or
80 ... 300 V DC

Wire cross section

max. 2.5 mm

2

Working temperature

–25 ... +70°C

For more technical data see the Data Sheet 679.D.101.xx

- Specifications subject to change without notice; date of issue 03/15 -