Entering CT ratio
The current transformer ratio CT must only be adjusted beetween 1 and 1999.
Example: With installed CTs 5000 A / 5 A, CT = 1000 must be adjusted.
Enter device settings
Enter PIN (see page above)
Select
CT
Enter the
CT
menu
Select digit (lit decimal point)
Adjust value
Adjust further digits in the same way, if necessary.
Confirm
Note:
Display may be wrong with a rated current of 5 A and a set CT ratio of more than
1999.
Resetting energy counters
Enter device settings
Enter PIN (see page above)
Select
CLEr
Enter the
CLEr
menu
Adjust confirmation:
no
= No,
YES
= Yes
Confirm
The energy counters are reset.
Display is set back from
YES
to
no
.
Technical Data
Dimensions
Electrical connection
Bezel
□
96 mm
Rated voltage
230/400 V
Bezel height
12 mm
Rated current
5 A
Panel cutout
□
90
+0.5
mm
Current connection
via CTs N/5 A
Weight
0.5 kg approx.
Auxiliary supply
85 ... 265 V AC or
80 ... 300 V DC
Wire cross section
max. 2.5 mm
2
Working temperature
–25 ... +70°C
For more technical data see the Data Sheet 679.D.101.xx
- Specifications subject to change without notice; date of issue 03/15 -