Page
81
February 2010
When upgrade is completed, the System Tools webpage will be shown if “Save to Flash”
was clicked. If “Save to Flash and Reset” was clicked, the unit will display a message
that the module is resetting.
Firmware upgrade is now complete.
Manual Upgrade using Flash Update
1.
Connect the module’s ethernet port to PC ethernet port via a “straight through” ethernet
cable. “Straight through” ethernet cable is typically a blue colour.
Alternatively, connect the module to PC via a network switch or hub, as some
configurations of Windows can encounter difficulty upgrading without a hub connected.
On some PCs, Windows can take much longer than expected to initialise its network
interface when the device is reset - connecting via a hub/switch removes this issue during
the upgrade procedure.
2.
Switch dip-switch on module to
SETUP
mode.
3.
Power up
the module and wait a couple seconds. This will ensure that Windows
networking can correctly detect an operating ethernet port.