Page
65
February 2010
Set dipswitch to RUN
Save the changes and unit will restart with new settings.
Client 1 Configuration
Perform the same configuration steps as the Access Point configuration with the following
differences:
•
set the Ethernet and Wireless IP addresses of WI-MOD-E to 192.168.0.201
•
set the Operating Mode to Client.
Ensure the same System Generator String is used and the same Radio Encryption method is
selected.
Client 2 Configuration
•
As above, however set the Ethernet and Wireless IP addresses as 192.168.0.202
Alternate procedure
– Adjust WI-MOD-E network settings using serial port (assuming
configuration PC is on existing network)
a)
Open terminal program with settings with data rate 19200bps, 8 data bits, 1 stop bit
and no parity.
b)
Set dipswitch to SETUP
c)
Connect straight through serial cable to WI-MOD-E and power up unit.
d)
When prompted, strike the Enter key to abort automatic boot
e)
Set IP address of WI-MOD-E to 192.168.0.200 with command bip 192.168.0.200
f)
Set netmask of WI-MOD-E to 192.168.0.200 with command bnm 255.255.255.0
g)
Set gateway address of WI-MOD-E to 192.168.0.1 with command bgw 192.168.0.1
h)
Set dipswitch to RUN
i)
Reset WI-MOD-E with reset command.
j)
Open configuration webpage with Internet Explorer at address http://192.168.0.200/
When prompted for password, enter default username “user” and password “user”
Enter “Network”, and select Operating Mode as Access Point.
Select Device Mode as Bridge.
Change the IP address to 192.168.0.200
Enter a System Address (SSID) string
Select the Radio Encryption required, and enter the system keys. Make a record of these
Encryption keys and use these on all modules in the system.
Set dipswitch to RUN
Save the changes and unit will restart with new settings.