Page
45
February 2010
If radio links are chained together to form a radio backbone, it is also important to consider the
operation of the Layer 3 Transparent Bridge (Refer Section 3.7). A WI-MOD-E Client will act as a
MAC Address translator, as it acts as a MAC address proxy on behalf of devices connected to its
wired Ethernet port. Addition of WI-MOD-E Client MAC addresses into intermediate WI-MOD-E
units’ whitelist filters may be required for correct operation.
It is advisable to use the Apply Changes button to test the configuration entered. Once the
configuration is determined to be correct, the Apply Changes and Save button should be used. In
the event that the configuration is incorrect, a power reset will revert the unit to previously saved
configuration.
If an erroneous configuration has prevented all access to the module, SETUP mode may be
used analyze what is wrong with the configuration.
Simply switch the dipswitch to SETUP and
cycle power. The WI-MOD-E will retain its configuration, however will load up at IP address
192.168.0.1XX, netmask 255.255.255.0 with the radio and filter disabled. The
XX in the IP address
is the last two digits of the serial number. Configuration webpages will still show the original
configuration. No changes are made to configuration until the user saves changes. To resume
normal operation, set the dipswitch to RUN and cycle power.
MAC Address Filter Configuration:
Add Entries
Enter the MAC addresses of devices to be added to the list. Multiple
entries must be separated by a semi-colon (;).
Delete Entries
Check the box alongside entries selected for removal from the list.
Whitelist or Blacklist
Check the box to make the list a whitelist. This will allow devices
with the MAC addresses listed to communicate with the module and
utilize the radio link. All other devices are blocked unless they exist
in an IP whitelist.
Uncheck the box to make the list a blacklist. This will prevent all
listed devices from using accessing the module and using the radio
link.
Apply Changes
Update settings.
Apply Changes and Save Update settings and save to non-volatile memory.