WI-GTWY-9-xxx Wireless Gateway V1.18
54
Update Times
To change the update times of
output mappings, select the
Update Times option. Any
I/O registers that have already
been mapped to remote
outputs will automatically be
listed. The default update
time is 10 minutes.
Changing Multiple Settings
You can change the Comms
Fail Times or Update Times of several I/O points simultaneously by using the <Shift> Select
feature. For example, if you want to change all times to 1 minute, you could change each
individually, or you could “block” all entries using the “Shift” Select feature and select “Edit”.
You only need to enter the change once to change all of the inputs selected. This feature is also
available with the other configurable parameters.
4.4.3
Don’t Send if in Comm Fail
You can configure a special “Don’t Send if in Comms Fail” mapping. If this is configured for a
particular remote module, the WI-GTWY-9-xxx will not transmit output messages to this remote
address, if there is a communications failure status on any input or output configured for the
same remote address. Output messages will re-start when a message is received from the remote
module. The use of this option can prevent the radio channel becoming congested if there are
many outputs at that module.
To configure this special mapping, select the “New Don’t Send in Comms Fail Mapping” box.
You will be asked to select which remote module this function applies to. You can enter more
than one of these mappings if there are more than one modules.