8 Diagnostics
| LED displays and troubleshooting
33
2599890000/01/03.2020
Manual UR67-PROFINET-V14
8.3 LED displays and troubleshooting
The module's parameter settings influence the behaviour of
the LED displays (see chapter 6.4).
LED
Status
Recommended measures
Module
U
S1
green: U
S1
≥ 20.4 V
orange: 20.4 V > U
S1
≥ 19.2 V
–
Check supply voltage
red: 19.2 V > U
S1
> ~12 V
–
Check supply voltage
off: U
S1
< ~12 V
–
Check supply voltage
U
S2
green: U
S2
≥ 20.4 V
orange: 20.4 V > U
S2
≥ 19.2 V
–
Check supply voltage
red: 19.2 V > U
S2
> ~12 V
–
Check supply voltage
off: U
S1
< ~12 V
–
Check supply voltage
BF
red: no fieldbus connection
–
Check Ethernet cable
–
Check PLC configuration
–
Check device name
Flashing red:
–
Configuration error
–
No connection to control unit
–
Error in parameter set
–
Check that the GSDML file is up to date
–
Check the fieldbus parameters and the PLC configuration
SF
Red:
–
Configuration error
–
Module error
–
New diagnostic message appears
–
Check that the GSDML file is up to date
–
Read off the diagnostic message from the web server or
engineering tool and determine which further actions to
take
Flashing red: module is in Force mode
LNK1/ACT1
Green: connection established between port XF1 of the
module and another field device
Flashing green: locating PROFINET devices
Flashing orange: data being exchanged on port XF1
LNK2/ACT2
Green: connection established between port XF2 of the
module and another field device
Flashing green: locating PROFINET devices
Flashing orange: data being exchanged on port XF2
POF DIA
Green: signal OK
Orange: maintenance requirement (POF system reserve <
2 dB)
–
Replace POF cable
Red: maintenance request (POF system reserve < 0 dB)
–
Replace POF cable
TEST
Flashing white: locating PROFINET devices