5
DETAILED PARAMETER DESCRIPTION
P0244 - Analog input AI3 offset (bipolar EBB board)
Adjustable range:
-100.0 to 100.0 %
Factory setting:
0.0 %
Acesso:
Menu
→
Configurations
→
I/O
→
Analog inputs
Description:
Refer to P0234.
P0245 - Analog input AI4 gain (bipolar EBA board)
Adjustable range:
0.000 to 9.999
Factory setting:
1.000
Acesso:
Menu
→
Configurations
→
I/O
→
Analog inputs
Description:
Refer to P0234.
✓
NOTE!
Analog Input located on the EBA Optional Board. Refer to the
Chapter 7 OPTIONAL ACCESSORIES
AND BOARDS on page 7-1
of the User’s Manual.
P0246 - AI4 Signal Type
Adjustable range:
0 to 4
Factory setting:
0
Acesso:
Menu
→
Configurations
→
I/O
→
Analog inputs
Description:
Set the S2.1 switch on the EBB optional board to “ON” position when a current signal is used at the analog
input AI4.
Inverse reference is obtained with the options 2 and 3, i.e., the maximum speed is obtained with the minimum
reference.
Table 5.42:
AI4 Signal Type
Function
0
(0 to 10) V/(0 to 20) mA
1
(4 to 20) mA
2
(10 to 0) V/(20 to 0) mA
3
(20 to 4) mA
4
(-10 to +10) V
✓
NOTE!
This parameter can be changed only with the motor stopped.
P0247 - Analog input AI4 offset (bipolar EBA board)
Adjustable range:
-100.0 to 100.0 %
Factory setting:
0.0 %
Acesso:
Menu
→
Configurations
→
I/O
→
Analog inputs
Description:
Refer to P0234.